{"product_id":"2401l-output-module-triconex","title":"2401L Output Module | Triconex","description":"\u003cp\u003eThe Triconex \u003cstrong\u003e2401L\u003c\/strong\u003e is a specialized output module engineered for safety-instrumented system (SIS) applications. It executes high-precision 12-bit digital-to-analog conversion to translate digital control logic into accurate 0-10 VDC output signals, providing robust signal isolation and continuous diagnostic monitoring for critical industrial processes.\u003c\/p\u003e\n\u003ch3\u003eSignal Performance and Isolation\u003c\/h3\u003e\n\u003cp\u003eThe module delivers an output accuracy of +\/-0.1% of full scale with a fast response time of under 2 ms. It incorporates 1500 VDC optical isolation to protect the system backplane from field-side electrical surges and maintains stable loop operation across industrial environments.\u003c\/p\u003e\n\u003ch3\u003eField Installation Guidelines\u003c\/h3\u003e\n\u003col\u003e\n\u003cli\u003eEnsure the system power is completely disconnected before inserting or removing the module from the rack.\u003c\/li\u003e\n\u003cli\u003eHandle the module using proper ESD precautions to prevent damage to sensitive internal circuitry.\u003c\/li\u003e\n\u003cli\u003eVerify that all field wiring is properly shielded and grounded to prevent ground loops and EMI, especially in high-noise industrial environments.\u003c\/li\u003e\n\u003cli\u003eConfirm that the module is fully seated in the backplane connector before applying power to ensure reliable communication.\u003c\/li\u003e\n\u003cli\u003eMaintain adequate ventilation around the chassis to support heat dissipation within the specified operating temperature range.\u003c\/li\u003e\n\u003c\/ol\u003e\n\u003cfigure class=\"table\"\u003e\n\u003ctable\u003e\n\u003cthead\u003e\n\u003ctr\u003e\n\u003cth\u003e\u003cstrong\u003eParameter\u003c\/strong\u003e\u003c\/th\u003e\n\u003cth\u003e\u003cstrong\u003eSpecification\u003c\/strong\u003e\u003c\/th\u003e\n\u003c\/tr\u003e\n\u003c\/thead\u003e\n\u003ctbody\u003e\n\u003ctr\u003e\n\u003ctd\u003eModel\u003c\/td\u003e\n\u003ctd\u003e2401L\u003c\/td\u003e\n\u003c\/tr\u003e\n\u003ctr\u003e\n\u003ctd\u003eBrand\u003c\/td\u003e\n\u003ctd\u003eTriconex\u003c\/td\u003e\n\u003c\/tr\u003e\n\u003ctr\u003e\n\u003ctd\u003eProduct Type\u003c\/td\u003e\n\u003ctd\u003eOutput Module\u003c\/td\u003e\n\u003c\/tr\u003e\n\u003ctr\u003e\n\u003ctd\u003eSignal Range\u003c\/td\u003e\n\u003ctd\u003e0-10 VDC\u003c\/td\u003e\n\u003c\/tr\u003e\n\u003ctr\u003e\n\u003ctd\u003eResolution\u003c\/td\u003e\n\u003ctd\u003e12-bit\u003c\/td\u003e\n\u003c\/tr\u003e\n\u003ctr\u003e\n\u003ctd\u003eAccuracy\u003c\/td\u003e\n\u003ctd\u003e+\/-0.1% of full scale\u003c\/td\u003e\n\u003c\/tr\u003e\n\u003ctr\u003e\n\u003ctd\u003eResponse Time\u003c\/td\u003e\n\u003ctd\u003e\u0026lt; 2 ms\u003c\/td\u003e\n\u003c\/tr\u003e\n\u003ctr\u003e\n\u003ctd\u003eIsolation\u003c\/td\u003e\n\u003ctd\u003e1500 VDC\u003c\/td\u003e\n\u003c\/tr\u003e\n\u003ctr\u003e\n\u003ctd\u003eInput Impedance\u003c\/td\u003e\n\u003ctd\u003e250 Ohms\u003c\/td\u003e\n\u003c\/tr\u003e\n\u003ctr\u003e\n\u003ctd\u003eMax Current\u003c\/td\u003e\n\u003ctd\u003e2 A @ 24 VDC\u003c\/td\u003e\n\u003c\/tr\u003e\n\u003ctr\u003e\n\u003ctd\u003ePower Consumption\u003c\/td\u003e\n\u003ctd\u003e20 W\u003c\/td\u003e\n\u003c\/tr\u003e\n\u003ctr\u003e\n\u003ctd\u003eOperating Temp\u003c\/td\u003e\n\u003ctd\u003e-40 to 70 deg C\u003c\/td\u003e\n\u003c\/tr\u003e\n\u003c\/tbody\u003e\n\u003c\/table\u003e\n\u003c\/figure\u003e\n\u003cp\u003eFrequently Asked Questions\u003c\/p\u003e\n\u003cp\u003eQ: What is the primary function of the 2401L module?\u003c\/p\u003e\n\u003cp\u003eA: It acts as an analog output module that converts digital signals from the Triconex safety system into 0-10 VDC commands for field devices.\u003c\/p\u003e\n\u003cp\u003eQ: Does this module require external power?\u003c\/p\u003e\n\u003cp\u003eA: Yes, the module consumes a maximum of 2 A at 24 VDC, so ensure your power supply is rated to handle the rack load.\u003c\/p\u003e","brand":"Triconex","offers":[{"title":"Default Title","offer_id":68171238965544,"sku":"2401L","price":327.0,"currency_code":"USD","in_stock":true}],"thumbnail_url":"\/\/cdn.shopify.com\/s\/files\/1\/0827\/6266\/2184\/files\/2401L.png?v=1794477906","url":"https:\/\/www.powerdcs.com\/ar\/products\/2401l-output-module-triconex","provider":"Power DCS Parts Limited","version":"1.0","type":"link"}