8C-TDOLA1 Digital Output IOTA | Honeywell
Specifications
Manufacturer: Honeywell
Product No.: 8C-TDOLA1
Condition: 10 العناصر الموجودة في المخزون
Product Type: Digital Output Cards
Product Origin: USA
Payment:T/T, Western Union
Weight: 450g
Shipping port: Xiamen
Warranty: 12 months
تفاصيل المنتج
وصف
The Honeywell 8C-TDOLA1, also cataloged as the 8C-TDOLA1 Digital Output Module, operates as a dedicated hardware component for 32-channel sourcing discrete signal drive execution within Honeywell Experion LX platforms.
Hardware Specifications
| Parameter | Specification |
|---|---|
| Model | 8C-TDOLA1 |
| Brand | Honeywell |
| Origin | USA |
| Operating Temp | 0 to 60 deg C |
| Power Consumption | 105 mA module current draw |
| Output Channels | 32 source-type digital outputs |
| Rated Voltage | 24 VDC |
| Max Load Voltage | 30 VDC |
| Max Load Current | 100 mA per channel |
| Short-Circuit Protection | Integrated per channel |
| Fuse Configuration | 4 fuses (1 per 8 channels) |
| Isolation | 1000 VAC system to field (with external power) |
| Storage Temp | -40 to 85 deg C |
Channel-to-Channel Isolation & Output Drive Dynamics
The 8C-TDOLA1 incorporates a 1000 VAC isolation barrier between system backplane logic and field-side terminal circuits. Engineered to interface with discrete field actuators and 4-20 mA HART loop protocol environments, the module delivers 32 independent source-type digital outputs at up to 100 mA per channel. Individual short-circuit protection combined with a 4-fuse grouping architecture (one fuse per 8 channels) limits field-side fault propagation, shielding central controller buses from transient overload states.
Frequently Asked Questions
Q: What protection is provided if a field wiring short circuit occurs on an output channel?
A: Each output channel features built-in electronic short-circuit protection, augmented by four internal fuses that each protect an 8-channel branch circuit.
Q: What isolation rating exists between the system backplane and field-side wiring on the 8C-TDOLA1?
A: The module provides 1000 VAC galvanic isolation between the internal system logic and field output circuits when using an external field power supply.
Field Installation Guidelines
- Disconnect all 24 VDC external power sources before mounting or removing the module from the IOTA terminal assembly base.
- Route discrete output field cables in dedicated raceways physically separated from high-voltage AC conductors.
- Verify that channel load current draw does not exceed 100 mA per point to prevent blowing the branch circuit fuse blocks.
- Secure signal cable shields and establish a single-point earth ground connection at the cabinet ground bar to prevent ground loops.