Configured for power conversion and voltage rail distribution within ControlEdge HC900 process and safety control systems, the Honeywell 900P24-0301, also cataloged as the 900P24-0301 DC/DC Converter Power Supply Module, provides direct physical/electrical execution.
Hardware Specifications
| Parameter | Specification |
|---|---|
| Model | 900P24-0301 |
| Brand | Honeywell |
| Origin | Standard Industrial Manufacturing |
| Weight | 0.8 kg |
| Dimensions | 137 mm x 72.6 mm x 42 mm |
| Operating Temp | Standard industrial cabinet range |
| Input Voltage Range | 21-29 VDC |
| Input Power Rating | 72.5 W |
| Output | Regulated 24 VDC, 60 W |
| Terminals | Screw-type, supports #12-22 AWG |
Channel-To-Channel Isolation And Loop Protocol Integrity
The module incorporates galvanic isolation barriers between primary DC input terminals and secondary regulated output rails to prevent common-mode noise and voltage transients from entering the backplane bus. It supports downstream 4-20 mA HART loop protocol power distribution requirements across connected I/O cards without introducing ground loops. Internal voltage regulation circuitry and cold junction compensation (CJC) reference stabilization protect system processing nodes against line voltage fluctuations and thermal drift.
Frequently Asked Questions
Q: Can multiple 900P24-0301 power supply modules be operated in parallel for redundant load sharing?
A: System architecture guidelines must be verified for the specific controller chassis, as direct paralleling requires dedicated isolation diodes or redundant power configuration modules to prevent reverse current loading.
Q: What precautions should be taken prior to extracting the DC/DC converter module?
A: Main DC input power feeding the cabinet distribution panel must be completely isolated, locked out, and tagged out before disconnecting wiring harnesses or unseating the unit.
Field Installation Guidelines
- Verify that primary DC input power is isolated, locked out, and tagged out prior to handling or wiring the power supply module.
- Make a dedicated safety ground connection to the chassis ground terminal before energizing the module.
- Insert the keyed module securely into the designated HC900 rack slot, ensuring proper mechanical engagement with backplane power pins.
- Check input screw terminals and output wiring connections for secure mechanical clamping and proper insulation before applying operating power.