900P24-0301 | Honeywell | DC/DC Converter

Specifications

  • Manufacturer: Honeywell

  • Product No.: 900P24-0301

  • Condition: 10 العناصر الموجودة في المخزون

  • Product Type: Power Supply Modules

  • Payment:T/T, Western Union

  • Weight: 800g

  • Shipping port: Xiamen

  • Warranty: 12 months

تفاصيل المنتج

وصف

Configured for power conversion and voltage rail distribution within ControlEdge HC900 process and safety control systems, the Honeywell 900P24-0301, also cataloged as the 900P24-0301 DC/DC Converter Power Supply Module, provides direct physical/electrical execution.

Hardware Specifications

Parameter Specification
Model 900P24-0301
Brand Honeywell
Origin Standard Industrial Manufacturing
Weight 0.8 kg
Dimensions 137 mm x 72.6 mm x 42 mm
Operating Temp Standard industrial cabinet range
Input Voltage Range 21-29 VDC
Input Power Rating 72.5 W
Output Regulated 24 VDC, 60 W
Terminals Screw-type, supports #12-22 AWG

Channel-To-Channel Isolation And Loop Protocol Integrity

The module incorporates galvanic isolation barriers between primary DC input terminals and secondary regulated output rails to prevent common-mode noise and voltage transients from entering the backplane bus. It supports downstream 4-20 mA HART loop protocol power distribution requirements across connected I/O cards without introducing ground loops. Internal voltage regulation circuitry and cold junction compensation (CJC) reference stabilization protect system processing nodes against line voltage fluctuations and thermal drift.

Frequently Asked Questions

Q: Can multiple 900P24-0301 power supply modules be operated in parallel for redundant load sharing?

A: System architecture guidelines must be verified for the specific controller chassis, as direct paralleling requires dedicated isolation diodes or redundant power configuration modules to prevent reverse current loading.

Q: What precautions should be taken prior to extracting the DC/DC converter module?

A: Main DC input power feeding the cabinet distribution panel must be completely isolated, locked out, and tagged out before disconnecting wiring harnesses or unseating the unit.

Field Installation Guidelines

  • Verify that primary DC input power is isolated, locked out, and tagged out prior to handling or wiring the power supply module.
  • Make a dedicated safety ground connection to the chassis ground terminal before energizing the module.
  • Insert the keyed module securely into the designated HC900 rack slot, ensuring proper mechanical engagement with backplane power pins.
  • Check input screw terminals and output wiring connections for secure mechanical clamping and proper insulation before applying operating power.