CC-PAIH01 Experion PKS C300 Analog Input Module | Honeywell

Specifications

  • Manufacturer: Honeywell

  • Product No.: CC- PAIH01

  • Condition: 10 العناصر الموجودة في المخزون

  • Product Type: Analog Input Modules

  • Product Origin: USA

  • Payment:T/T, Western Union

  • Weight: 2000g

  • Shipping port: Xiamen

  • Warranty: 12 months

تفاصيل المنتج

وصف

The Honeywell CC-PAIH01, also cataloged as the CC-PAIH01 Analog Input with HART Module, operates as a dedicated hardware component for high-level current signal acquisition and digital field telemetry routing within Experion PKS C300 platforms.

Hardware Specifications

Parameter Specification
Model CC-PAIH01
Brand Honeywell
Origin USA
Weight 2 kg (shipping weight)
Dimensions Standard C300 I/O Module Dimensions
Operating Temp -40 to +70 deg C
Power Consumption 24 VDC bus powered
Functional Type High Level Analog Input with HART
Number of Channels 16 circuits
Input Channel Topology Supports differential inputs on channels 13 through 16
PMIO Equivalent Type HLAIHART
Protocol Support 4-20 mA HART loop protocol

4-20 mA HART Loop Protocol and Channel Isolation Execution

The Honeywell CC-PAIH01 processes 16 high-level analog current loops, maintaining continuous digital bidirectional data flow via the 4-20 mA HART loop protocol. Channels 13 through 16 incorporate dedicated differential input circuitry to suppress ground potential differences across complex instrumentation networks. The onboard signal conditioning channels enforce strict system-side galvanic isolation, preventing severe electrical noise and common-mode voltage surges from propagating into the core C300 controller backplane.

Frequently Asked Questions

Q: How are differential input configurations assigned on the CC-PAIH01 module?

A: Differential input capability is wired and assigned strictly to channels 13 through 16, whereas channels 1 through 12 operate under standard single-ended analog input signal topologies.

Q: Can the CC-PAIH01 module pass HART digital pass-through data to asset management software?

A: Yes, the onboard HART modem circuitry extracts digital primary, secondary, tertiary, and quaternary variables from the 4-20 mA analog loop signal and forwards them over the backplane to Experion PKS asset management tools.

Q: Is this module hot-swappable on an active C300 IOTA baseplate?

A: Yes, the hardware supports online insertion and removal (hot-swapping) on an energized IOTA without disrupting backplane communications or requiring a controller restart.

Field Installation Guidelines

  1. Align the module rear connectors with the target slot on the C300 IOTA carrier and push firmly until the locking tabs snap into place.
  2. Route 4-20 mA loop cables through dedicated wire troughs, ensuring a minimum 200 mm clearance from high-voltage AC conductors to reduce electromagnetic interference.
  3. Connect signal cable shield drain wires to the cabinet grounding bar at a single termination point to eliminate ground loops.
  4. Verify field wiring polarity for 2-wire transmitter loops before energizing channel power rails.
  5. Provide a minimum vertical clearance zone of 100 mm above and below the assembly to allow natural thermal convection airflow across the housing.