CC-TAOX61 51307081-175 | Honeywell | Experion Series 8 Analog Output IOTA Board
Specifications
Manufacturer: Honeywell
Product No.: CC-TAOX61 51307081-175
Condition: 10 العناصر الموجودة في المخزون
Product Type: Analog Output Modules
Product Origin: USA
Payment:T/T, Western Union
Weight: 3000g
Shipping port: Xiamen
Warranty: 12 months
تفاصيل المنتج
وصف
The Honeywell CC-TAOX61 51307081-175, also cataloged as the CC-TAOX61 Analog Output IOTA Board, operates as a dedicated hardware component for 4-20 mA analog signal conversion within Honeywell Experion PKS C300 systems. It drives digital-to-analog control commands across Series 8 I/O termination structures to execute field valve positioning and actuator control.
Hardware Specifications
| Parameter | Specification |
|---|---|
| Model | CC-TAOX61 |
| Part Number | 51307081-175 |
| Brand | Honeywell |
| Origin | USA |
| Operating Temp | -40 deg C to +70 deg C |
| Power Consumption | Backplane bus powered via IOTA connection |
| Output Signal | 4-20 mA analog current loop |
| Channel Density | 16 channels |
| System Integration | Experion PKS C300 Series 8 I/O |
4-20 mA HART Loop Protocol Integration
The Honeywell CC-TAOX61 IOTA board executes digital-to-analog conversion across 16 independent current channels, providing regulated 4-20 mA current loops to drive electro-pneumatic valve positioners and variable speed drives. The internal circuit topology supports the 4-20 mA HART loop protocol by superimposing bidirectional FSK digital communication signals over the primary analog output current. Galvanic and channel-to-channel isolation mechanisms integrated into the IOTA layout suppress cross-channel noise and prevent circulating ground loop interference from affecting drive signal linearity.
Frequently Asked Questions
Q: Is the CC-TAOX61 board hot-swappable during active process control?
A: Yes, online module replacement is supported when installed on compatible Series 8 IOTA bases, provided the affected output loops are placed in a documented safe state.
Q: Does each output channel require an external loop power supply?
A: The board interfaces with system-supplied loop power; total channel load impedance must be validated against the 4-20 mA driver voltage limits to ensure full-scale current delivery.
Q: How does the CC-TAOX61 mitigate backplane noise interference from field cabling?
A: Integrated isolation circuitry between the field termination terminals and the system logic bus prevents high-voltage field transients and ground potential differences from propagating to the controller.
Field Installation Guidelines
- Mount the CC-TAOX61 IOTA board onto the cabinet carrier rail, verifying that the grounding spring clips make solid metallic contact with the enclosure chassis ground.
- Route 4-20 mA field output cables through separated wire channels, maintaining dedicated spacing from AC power cables to prevent electromagnetic coupling.
- Terminate signal conductors at the screw terminal block, ensuring correct polarity connection for each of the 16 independent output channels.
- Connect overall cable shields to the main enclosure ground bar at a single point to prevent ground loop currents from degrading HART digital communications.
- Align the corresponding Series 8 Analog Output module with the IOTA interface connectors and press firmly until the locking clips engage completely.