{"product_id":"foxboro-fbm203c-p0922ud-rtd-input-module","title":"Foxboro FBM203C P0922UD RTD Input Module","description":"\u003cp\u003eThe \u003cstrong\u003eFoxboro FBM203C P0922UD\u003c\/strong\u003e is an 8-channel RTD input module for the Schneider Electric Foxboro Evo System. It measures 2- or 3-wire RTD sensors across a 0 to 30 ohm range using independent per-channel sigma-delta A\/D conversion, galvanic isolation, software-configurable integration periods, and status LED indicators.\u003c\/p\u003e\n\u003ch3\u003eRTD Range, Excitation, and Lead Resistance\u003c\/h3\u003e\n\u003cp\u003eFor the \u003cstrong\u003eFBM203C\u003c\/strong\u003e (0 to 30 ohm range, where 30 ohms equals 64,000 counts and maximum overrange reaches 30.72 ohms at 65,535 counts), nominal sensor excitation current is 0.54 mA DC. In comparison, the listed FBM203\/203D range covers 0 to 320 ohms (64,000 counts at 320 ohms; 327.675 ohms max overrange at 65,535 counts) at 0.19 mA DC nominal.\u003c\/p\u003e\n\u003cp\u003eAllowable lead resistance on \u003cstrong\u003eFBM203C\u003c\/strong\u003e is up to 10 ohms maximum per lead, and lead resistance imbalance degrades measurement accuracy. By contrast, FBM203 allows up to 50 ohms per lead with imbalance affecting accuracy, while FBM203D allows up to 50 ohms per lead without imbalance affecting accuracy.\u003c\/p\u003e\n\u003ch3\u003eConversion, Noise Rejection, and Maintenance\u003c\/h3\u003e\n\u003cp\u003eEach channel uses an independent sigma-delta A\/D converter with a software-configurable integration period and a 25 ms update interval for new values. Accuracy including linearity is +\/- 0.1% of span for \u003cstrong\u003eFBM203C\u003c\/strong\u003e (compared with +0.03% of span listed for FBM203\/203D), with a temperature coefficient of +\/- 50 ppm\/deg C.\u003c\/p\u003e\n\u003cp\u003eGalvanic isolation separates each input channel to limit interference, supported by common mode rejection greater than 125 dB at 50 or 60 Hz and normal mode rejection greater than 95 dB at 50 or 60 Hz. Red and green LED indicators show module status, and modules can be replaced without disconnecting field cables.\u003c\/p\u003e\n\u003ch3\u003eTechnical Specifications\u003c\/h3\u003e\n\u003cfigure class=\"table\"\u003e\n\u003ctable\u003e\n\u003cthead\u003e\n\u003ctr\u003e\n\u003cth\u003e\u003cstrong\u003eParameter\u003c\/strong\u003e\u003c\/th\u003e\n\u003cth\u003e\u003cstrong\u003eSpecification\u003c\/strong\u003e\u003c\/th\u003e\n\u003c\/tr\u003e\n\u003c\/thead\u003e\n\u003ctbody\u003e\n\u003ctr\u003e\n\u003ctd\u003eModel\u003c\/td\u003e\n\u003ctd\u003eFBM203C P0922UD\u003c\/td\u003e\n\u003c\/tr\u003e\n\u003ctr\u003e\n\u003ctd\u003eBrand\u003c\/td\u003e\n\u003ctd\u003eFoxboro\u003c\/td\u003e\n\u003c\/tr\u003e\n\u003ctr\u003e\n\u003ctd\u003eSystem \/ Series\u003c\/td\u003e\n\u003ctd\u003eFoxboro Evo System\u003c\/td\u003e\n\u003c\/tr\u003e\n\u003ctr\u003e\n\u003ctd\u003eInput Channels\u003c\/td\u003e\n\u003ctd\u003e8 isolated and independent channels (2- or 3-wire RTD sensors)\u003c\/td\u003e\n\u003c\/tr\u003e\n\u003ctr\u003e\n\u003ctd\u003eInput Range\u003c\/td\u003e\n\u003ctd\u003e0 to 30 ohm (30 ohm = 64,000 counts; max overrange 30.72 ohm at 65,535 counts)\u003c\/td\u003e\n\u003c\/tr\u003e\n\u003ctr\u003e\n\u003ctd\u003eSensor Current\u003c\/td\u003e\n\u003ctd\u003e0.54 mA DC nominal\u003c\/td\u003e\n\u003c\/tr\u003e\n\u003ctr\u003e\n\u003ctd\u003eLead Resistance Limit\u003c\/td\u003e\n\u003ctd\u003e10 ohm maximum per lead (imbalance decreases accuracy)\u003c\/td\u003e\n\u003c\/tr\u003e\n\u003ctr\u003e\n\u003ctd\u003eAnalog Accuracy\u003c\/td\u003e\n\u003ctd\u003e+\/- 0.1% of span (includes linearity)\u003c\/td\u003e\n\u003c\/tr\u003e\n\u003ctr\u003e\n\u003ctd\u003eTemperature Coefficient\u003c\/td\u003e\n\u003ctd\u003e+\/- 50 ppm\/deg C\u003c\/td\u003e\n\u003c\/tr\u003e\n\u003ctr\u003e\n\u003ctd\u003eA\/D Conversion\u003c\/td\u003e\n\u003ctd\u003eIndependent sigma-delta conversion per channel; 25 ms new value interval\u003c\/td\u003e\n\u003c\/tr\u003e\n\u003ctr\u003e\n\u003ctd\u003eIntegration Period\u003c\/td\u003e\n\u003ctd\u003eSoftware configurable\u003c\/td\u003e\n\u003c\/tr\u003e\n\u003ctr\u003e\n\u003ctd\u003eCommon Mode Rejection\u003c\/td\u003e\n\u003ctd\u003eGreater than 125 dB at 50 or 60 Hz\u003c\/td\u003e\n\u003c\/tr\u003e\n\u003ctr\u003e\n\u003ctd\u003eNormal Mode Rejection\u003c\/td\u003e\n\u003ctd\u003eGreater than 95 dB at 50 or 60 Hz\u003c\/td\u003e\n\u003c\/tr\u003e\n\u003ctr\u003e\n\u003ctd\u003eStatus Indicators\u003c\/td\u003e\n\u003ctd\u003eRed and green LEDs\u003c\/td\u003e\n\u003c\/tr\u003e\n\u003c\/tbody\u003e\n\u003c\/table\u003e\n\u003c\/figure\u003e\n\u003cp\u003eFrequently Asked Questions\u003c\/p\u003e\n\u003cp\u003eQ: How does lead resistance affect the Foxboro FBM203C P0922UD compared with FBM203 and FBM203D?\u003c\/p\u003e\n\u003cp\u003eA: The \u003cstrong\u003eFBM203C\u003c\/strong\u003e supports up to 10 ohm maximum per lead and lead resistance imbalance reduces accuracy. By comparison, FBM203 and FBM203D are rated up to 50 ohm maximum per lead, with imbalance affecting FBM203 accuracy but not FBM203D accuracy.\u003c\/p\u003e\n\u003cp\u003eQ: What is the input range and sensor current for the FBM203C P0922UD?\u003c\/p\u003e\n\u003cp\u003eA: Its input range is 0 to 30 ohm (30.72 ohm max overrange at 65,535 counts) with a nominal sensor current of 0.54 mA DC.\u003c\/p\u003e\n\u003cp\u003eQ: Can the module be serviced without disconnecting field wiring?\u003c\/p\u003e\n\u003cp\u003eA: Yes, the specification indicates modules can be replaced without disconnecting cables, and red and green LEDs display module status.\u003c\/p\u003e","brand":"Foxboro","offers":[{"title":"Default Title","offer_id":68249514311976,"sku":"FBM203C P0922UD","price":238.0,"currency_code":"USD","in_stock":true}],"thumbnail_url":"\/\/cdn.shopify.com\/s\/files\/1\/0827\/6266\/2184\/files\/FBM203CP0922UD.png?v=1795140629","url":"https:\/\/www.powerdcs.com\/ar\/products\/foxboro-fbm203c-p0922ud-rtd-input-module","provider":"Power DCS Parts Limited","version":"1.0","type":"link"}