Foxboro FBM230 P0926GU Field Device System Integrator Module

Specifications

  • Manufacturer: Foxboro

  • Product No.: FBM230 P0926GU

  • Condition: 10 العناصر الموجودة في المخزون

  • Product Type: Field Device System Integrator Modules

  • Product Origin: USA

  • Payment:T/T, Western Union

  • Weight: 350g

  • Shipping port: Xiamen

  • Warranty: 12 months

تفاصيل المنتج

وصف

The FBM230 P0926GU is a Foxboro I/A Series field device system integrator module with four software-configurable serial ports for RS-232, RS-422, or RS-485 communications. Powered by redundant 24 VDC (+5%, -10%) with a 7 W maximum draw, it links external serial devices to Foxboro control databases over a redundant 2 Mbps module fieldbus.

Serial Ports, Capacity, and Protocol Drivers

Each of the four serial ports on the FBM230 P0926GU can be configured independently in software for RS-232, RS-422, or RS-485 operation. I/O software drivers can be downloaded from a library of supported protocols to integrate field device data into a Foxboro control database.

The module supports up to 200 DCI block connections and handles up to 64 RS-485 devices or up to 4 direct-connect RS-232 or RS-422 devices. Plan port assignments and device counts around protocol overhead and serial bus topology limits during system engineering.

System Bus, Power, and Cabling Limits

On the system side, the FBM230 P0926GU communicates over a redundant 2 Mbps module fieldbus with associated FCM100ET, FCM100E, FCP270, or FCP280 modules. Redundant 24 VDC input power is rated for +5%, -10% tolerance with up to 7 W power consumption and 7 W heat dissipation.

Termination assemblies connect to the module via Type 5 termination cables in lengths from 1 m (3.2 ft) to 5 m (16.4 ft). Field cable runs reach up to 15 m (50 ft) for custom EIA RS-232 DB-25 connections to modems, converters, or devices, and up to 1200 m (3937 ft) for RS-422 and RS-485 links.

Environmental and Mechanical Considerations

The module is designed for field mounting and rated for Class G3 harsh environments, operating from -20 deg C to +70 deg C (-4 deg F to +158 deg F) with 5% to 95% non-condensing relative humidity. Storage temperature spans -40 deg C to +70 deg C (-40 deg F to +158 deg F) under 5% to 95% non-condensing humidity.

Module dimensions are 102 mm (4 in) high—114 mm (4.5 in) with mounting lugs—by 45 mm (1.75 in) wide by 104 mm (4.11 in) deep, with an approximate mass of 284 g (10 oz). Listed termination assemblies include ring lug P0926PA (approximately 363 g / 0.8 lb) and compression screw RH926GH (approximately 272 g / 0.6 lb).

Technical Specifications

Parameter Specification
Model FBM230 P0926GU
Brand Foxboro
Product Type Field Device System Integrator Module
Series I/A Series
Serial Ports 4 ports, individually configurable in software for RS-232, RS-422, or RS-485
Device Capacity Up to 64 RS-485 devices or up to 4 direct-connect RS-232 or RS-422 devices
DCI Block Capacity Up to 200 DCI block connections
Module Fieldbus Redundant 2 Mbps module fieldbus
Associated Modules FCM100ET, FCM100E, FCP270, or FCP280
Input Voltage Range (Redundant) 24 VDC (+5%, -10%)
Power Consumption 7 W maximum
Heat Dissipation 7 W maximum
Termination Cable Type 5, 1 m (3.2 ft) to 5 m (16.4 ft) between FBM230 and TA
Field Cable Distance Up to 15 m (50 ft) custom RS-232 (DB-25); up to 1200 m (3937 ft) RS-422 and RS-485
Termination Assemblies Ring Lug P0926PA (approx. 363 g / 0.8 lb); Compression Screw RH926GH (approx. 272 g / 0.6 lb)
Module Dimensions 102 mm (4 in) H (114 mm / 4.5 in with mounting lugs) x 45 mm (1.75 in) W x 104 mm (4.11 in) D
Module Mass Approx. 284 g (10 oz)
Operating Temperature -20 deg C to +70 deg C (-4 deg F to +158 deg F)
Storage Temperature -40 deg C to +70 deg C (-40 deg F to +158 deg F)
Relative Humidity 5% to 95%, non-condensing
Environmental Rating Class G3

Frequently Asked Questions

Q: How many serial devices can the Foxboro FBM230 P0926GU connect to?

A: It supports up to 64 RS-485 devices or up to 4 direct-connect RS-232 or RS-422 devices across its four software-configurable ports, within a limit of up to 200 DCI block connections. Actual device counts also depend on the selected protocol driver and serial network layout.

Q: Which termination assemblies and cable lengths apply to the FBM230 P0926GU?

A: The source lists ring lug termination assembly P0926PA and compression screw termination assembly RH926GH, connected via Type 5 cables from 1 m (3.2 ft) to 5 m (16.4 ft). Field runs can extend up to 15 m (50 ft) for custom RS-232 DB-25 links and up to 1200 m (3937 ft) for RS-422 and RS-485.

Q: What power supply and fieldbus connections does the FBM230 P0926GU use?

A: It uses redundant 24 VDC (+5%, -10%) power at up to 7 W maximum and communicates over a redundant 2 Mbps module fieldbus with FCM100ET, FCM100E, FCP270, or FCP280 modules. Verify power redundancy and fieldbus compatibility within your Foxboro I/A Series configuration.

كيفية الحصول على عرض أسعار

تتبع الطلب

شركات الشحن

سياسة وشروط الاسترداد

شروط الضمان

منتجات ذات صله