HART Input Interface Module | Foxboro P0922VT FBM214
Specifications
Manufacturer: Foxboro
Product No.: P0922VT
Condition: 10 العناصر الموجودة في المخزون
Product Type: Analog Input Modules
Product Origin: USA
Payment:T/T, Western Union
Weight: 284g
Shipping port: Xiamen
Warranty: 12 months
تفاصيل المنتج
وصف
Foxboro P0922VT FBM214 HART Input Interface Module
The Foxboro P0922VT, also cataloged as the FBM214 HART Communication Input Interface Module, operates as a dedicated hardware component for 8-channel analog signal acquisition and digital device diagnostics within Foxboro I/A Series DCS platforms.
Hardware Specifications
| Parameter | Specification |
|---|---|
| Model | P0922VT |
| Brand | Foxboro (Schneider Electric) |
| Origin | USA |
| Weight | 0.284 kg (0.60 lbs) |
| Dimensions | 10.4 cm x 10.2 cm x 4.5 cm |
| Operating Temp | -20 to +60 deg C |
| Power Consumption | 7 W maximum |
| Input Channels | 8 individually isolated channels |
| Input Signal | 4-20 mA DC with HART Protocol Version 6 |
| A/D Resolution | 15-bit |
| Accuracy | +/-0.03% of full scale |
| Fieldbus | Redundant 2 Mbps Fieldbus |
| Mounting | Modular baseplate (DIN rail or 19-inch rack) |
Process Control Instrumentation Features
The Foxboro P0922VT processes standard 4-20 mA HART loop protocol communications by demodulating HART FSK digital signals superimposed on the primary analog current loops. Its channel-to-channel isolation architecture protects signal integrity against ground loops and common-mode voltage fluctuations across all eight inputs. An integrated analog-to-digital converter delivers 15-bit resolution with an update rate of 100 ms, while internal loop power circuitry supplies 24 VDC to connected smart transmitters. Furthermore, cold junction compensation (CJC) reference handling integrates seamlessly when interfacing temperature transmitters across the fieldbus network.
Frequently Asked Questions
Q: How does the P0922VT FBM214 module execute HART digital communication alongside analog sampling?
A: The module superimposes 1200 baud FSK digital signals directly over the 4-20 mA current loop, allowing simultaneously 2 digital messages per second without disturbing the primary analog measurement.
Q: Can the P0922VT module operate on a standard DIN rail without baseplate hardware?
A: No, the module requires a dedicated Foxboro modular baseplate, which itself mounts onto a horizontal or vertical DIN rail or a 19-inch rack enclosure.
Field Installation Guidelines
Mounting the Foxboro P0922VT requires installing the modular baseplate onto a standard DIN rail or 19-inch rack before inserting the module into its keyed baseplate slot. Ensure that dual 24 VDC power feeds and redundant 2 Mbps Fieldbus cables are firmly connected to the backplane prior to powering the rack.