Honeywell 2MLF-AC4H MasterLogic ML200 Analog Input Module
Specifications
Manufacturer: Honeywell
Product No.: 2MLF-AC4H
Condition: 10 العناصر الموجودة في المخزون
Product Type: Analog Input Modules
Product Origin: USA
Payment:T/T, Western Union
Weight: 1200g
Shipping port: Xiamen
Warranty: 12 months
تفاصيل المنتج
وصف
The Honeywell 2MLF-AC4H is a 4-channel analog input module engineered for the MasterLogic ML200 PLC series. It processes current field signals with a high 1/64000 digital output resolution and enables bidirectional HART communication overlaid on standard 4-20 mA analog wiring without requiring separate digital networks.
Analog Signal Acquisition and HART Integration
The module accepts current input ranges of 4-20 mA (with HART protocol support) and 0-20 mA (without HART support). It achieves an accuracy of +/-0.1% at 25 deg C with a temperature coefficient of +/-0.25%, providing stable signal processing across ambient temperature fluctuations. Field signals connect via an 18-point terminal block connector.
The integrated HART interface enables remote device configuration, process variable access, and field instrument diagnostics directly through the primary signal pair.
Output Formatting and Diagnostics
Converted analog signals can be scaled into signed values (-32000 to 32000), precise values, or percentile representations (0 to 10000). The module features automatic input disconnection detection on the 4-20 mA range to detect open loop or sensor failure conditions.
Board assembly incorporates protective coating to safeguard components in harsh operating environments. Internal power draw is approximately 340 mA at 5 VDC from the system backplane rail.
Technical Specifications
| Parameter | Specification |
|---|---|
| Model | 2MLF-AC4H |
| Brand | Honeywell |
| Series | MasterLogic ML200 |
| Product Type | Analog Input Modules |
| Input Channels | 4 channels |
| Input Signal Range | 4-20 mA (HART supported), 0-20 mA (HART not supported) |
| Resolution | 1/64000 |
| Accuracy | +/-0.1% at 25 deg C |
| Temperature Coefficient | +/-0.25% |
| Communication Protocol | HART (bidirectional over 4-20 mA wiring) |
| Digital Output Formats | Signed Value (-32000 to 32000), Precise Value, Percentile (0 to 10000) |
| Input Disconnection Detection | Supported (4-20 mA range) |
| Power Consumption | Approximately 340 mA at 5 VDC |
| Terminal Type | 18-point terminal block connector |
| Mounting Type | DIN rail or panel mount |
| Storage Temperature | -25 to +70 deg C |
| Operating Humidity | 5 to 95% RH (non-condensing) |
| Weight | 1.2 kg |
Frequently Asked Questions
Q: Is HART communication supported on both current input ranges of the 2MLF-AC4H module?
A: No, HART communication is supported exclusively on the 4-20 mA current loop range. It is not supported on the 0-20 mA range.
Q: How does the module indicate open field circuit or sensor failures?
A: It features built-in input disconnection detection that identifies loop breaks when operating within the 4-20 mA signal range.
Q: What output data formats can be selected for signal processing?
A: Converted values can be formatted as Signed Values (-32000 to 32000), Precise Values, or Percentile Values (0 to 10000).