Honeywell 8C-TAIXA1 51307127-175 Series 8 Analog Input Module
Specifications
Manufacturer: Honeywell
Product No.: 8C-TAIXA1 51307127-175
Condition: 10 العناصر الموجودة في المخزون
Product Type: Analog Input Modules
Product Origin: USA
Payment:T/T, Western Union
Weight: 300g
Shipping port: Xiamen
Warranty: 12 months
تفاصيل المنتج
وصف
Configured for high-precision analog signal digitization in Experion PKS Series 8 platforms, the Honeywell 8C-TAIXA1 51307127-175 (8C-TAIXA1 Analog Input Module) provides direct physical/electrical execution.
Hardware Specifications
| Parameter | Specification |
|---|---|
| Model | 8C-TAIXA1 51307127-175 |
| Brand | Honeywell |
| Origin | USA |
| Weight | 0.3 kg |
| Dimensions | 220 mm x 120 mm x 152.4 mm |
| Operating Temp | -20 to +70 deg C |
| Power Consumption | Unspecified (24 VDC system power) |
| Part Number | 51307127-175 |
| Module Type | Analog Input Module |
| Input Channels | 8 channels |
| Supported Signals | 4-20 mA, 0-10 V, resistive inputs |
| Input Range | Configurable (0-20 mA, 4-20 mA, 0-10 V) |
| Resolution | 16-bit ADC |
| Accuracy | +/-0.05% of full scale |
| Input Impedance | >250 ohm (current), >1 Mohm (voltage) |
| Response Time | <100 ms |
| System Isolation | Optical isolation between inputs and control system |
| Mounting | DIN rail or panel |
4-20 mA HART Loop Protocol & Channel-to-Channel Isolation
The 8C-TAIXA1 51307127-175 samples process variables across 8 input channels, using an onboard 16-bit analog-to-digital converter (ADC) with a signal response latency under 100 ms. Dedicated optical isolation barriers separate field wiring terminals from internal backplane circuitry, preventing high common-mode transients and ground potential differences from causing data corruption. When operating in 4-20 mA current mode, the module maintains an input impedance exceeding 250 ohm and passes bidirectional 4-20 mA HART loop protocol diagnostic digital data seamlessly to the controller platform without altering real-time process values.
Frequently Asked Questions
Q: How is the input signal type changed on individual channels of the 8C-TAIXA1 51307127-175?
A: Input signal modes (4-20 mA, 0-10 V, or resistive inputs) are configured per channel via system parameters in the Experion PKS engineering software.
Q: Does the 8C-TAIXA1 51307127-175 support hot-swapping during online operations?
A: Yes, the card supports removal and insertion under power (RIUP) on compatible Series 8 carriers without interrupting communications on adjacent active slots.
Q: What prevents electrical noise from affecting the 16-bit measurement accuracy?
A: High input impedance (>1 Mohm for voltage inputs) combined with optical isolation prevents earth ground loops and external field noise from impairing signal integrity.
Field Installation Guidelines
- Carrier Module Seat: Align the module edge connectors with the designated slot on the Series 8 carrier base and press firmly until side retaining latches snap shut.
- Shield Cable Termination: Connect field transmitter cable drain wires to a dedicated system earth grounding bar to minimize high-frequency noise interference.
- Cable Separation: Route low-level 4-20 mA and 0-10 V field wiring in isolated wiring ducts away from high-voltage AC cables and motor control leads.
كيفية الحصول على عرض أسعار