Honeywell CC-PAIH02 51405039-175 Experion PKS Analog Input Module
Specifications
Manufacturer: Honeywell
Product No.: CC-PAIH02 51405039-175
Condition: 10 العناصر الموجودة في المخزون
Product Type: Analog Input Modules
Product Origin: USA
Payment:T/T, Western Union
Weight: 450g
Shipping port: Xiamen
Warranty: 12 months
تفاصيل المنتج
وصف
Configured for high-level signal acquisition in Experion PKS Series-C control systems, the Honeywell CC-PAIH02 51405039-175 (CC-PAIH02 Analog Input Module) provides direct physical/electrical execution. It handles 16 analog input channels across Input/Output Termination Assembly (IOTA) backplane networks.
Hardware Specifications
| Parameter | Specification |
|---|---|
| Model | CC-PAIH02 51405039-175 |
| Brand | Honeywell |
| Origin | USA |
| Operating Temp | -40 to +70 deg C |
| Power Consumption | ~6 W typical |
| Part Number | 51405039-175 |
| Channels | 16 channels (12 single-ended, 4 differential) |
| Input Ranges | 0-5 V, 1-5 V, 0.4-2 V, 4-20 mA (via internal 250 ohm resistor) |
| Resolution | 16 bits |
| Scan Rate | 50 ms |
Channel-to-Channel Isolation and 4-20 mA HART Loop Protocol Execution
The Honeywell CC-PAIH02 51405039-175 analog input module digitizes process variables using a 16-bit A/D converter across a 50 ms scan rate cycle. Each channel interfaces directly with 2-wire or self-powered field transmitters utilizing the 4-20 mA HART loop protocol, as well as 0-5 V, 1-5 V, and 0.4-2 V voltage signals. The internal circuit architecture provides channel-to-channel isolation and common-mode noise suppression to safeguard backplane communications against field-side electrical interference and ground loop offsets.
Frequently Asked Questions
Q: How does the CC-PAIH02 51405039-175 module handle 4-20 mA current signals?
A: Current loop signals are converted internally across precision 250 ohm dropping resistors built into the module input circuit.
Q: Can single-ended and differential inputs be used simultaneously on the same CC-PAIH02 51405039-175 module?
A: Yes, the hardware layout supports up to 12 single-ended channels and 4 differential channels concurrently as designated on the corresponding IOTA terminal block.
Field Installation Guidelines
- Mount the Series-C IOTA base firmly onto the cabinet DIN rail or frame before seating the module.
- Align the module rear edge connector with the IOTA receptacle and press firmly until the mechanical locking tabs engage.
- Terminate field 4-20 mA or voltage signal conductors onto the assigned IOTA terminal terminals, checking for correct polarity.
- Route low-voltage analog input signal cabling in segregated wire troughs at least 200 mm away from high-voltage AC conductors.
- Ground signal cable shield drain wires at a single point on the cabinet earthing bus bar to prevent ground current loops.
كيفية الحصول على عرض أسعار
تتبع الطلب
شركات الشحن
سياسة وشروط الاسترداد
شروط الضمان
منتجات ذات صله
- يؤدي اختيار تحديد إلى تحديث كامل للصفحة.