Honeywell CC-PFB401 51405044-176 Fieldbus Interface Module
Specifications
Manufacturer: Honeywell
Product No.: CC-PFB401 51405044-176
Condition: 10 العناصر الموجودة في المخزون
Product Type: Fieldbus Interface Modules
Product Origin: USA
Payment:T/T, Western Union
Weight: 410g
Shipping port: Xiamen
Warranty: 12 months
تفاصيل المنتج
وصف
The Honeywell CC-PFB401, also cataloged as the CC-PFB401 Fieldbus Interface Module (Part Number: 51405044-176), operates as a dedicated hardware component for field device digital communication management within Honeywell Experion PKS Series C networks.
Hardware Specifications
| Parameter | Specification |
|---|---|
| Model | CC-PFB401 (Part Number: 51405044-176) |
| Brand | Honeywell |
| Origin | USA |
| Weight | 0.41 kg (0.90 lbs) |
| Dimensions | Standard Series C module enclosure |
| Operating Temp | -40 to +70 deg C housing environmental envelope |
| Power Consumption | 24 VDC, 210 mA |
| Physical Interface | H1 FOUNDATION Fieldbus (31.25 kbps) |
| Network Capacity | 4 H1 links per module (up to 16 devices per link) |
| Redundancy Support | Non-redundant or redundant (side-by-side) configuration |
| Macrocycle Periods | 250 ms, 500 ms, 1 sec, 2 sec, 4 sec, 8 sec, 16 sec, 32 sec |
| Status Indicators | 24V Power LED, Module & FTE Status LEDs, Front display panel |
| Coating | Conformally coated circuit assembly |
| Product Category | Fieldbus Interface Modules |
FOUNDATION Fieldbus Connectivity & Process Signal Isolation
The CC-PFB401 Series C FIM4 module interfaces up to four independent H1 FOUNDATION Fieldbus links operating at 31.25 kbps. The conformally coated circuit board incorporates channel-to-channel isolation barriers between the internal backplane logic and the field-side H1 segments. This isolation prevents ground potential shifts and high-frequency noise interference from disrupting deterministic execution across interconnected HART loop protocol devices and Fieldbus instruments, maintaining signal integrity over multi-drop field networks.
Frequently Asked Questions
Q: Does the CC-PFB401 support hot-swapping under live power conditions?
A: Yes, in a redundant side-by-side configuration, a faulty CC-PFB401 module can be unseated and replaced without interrupting communication on the active secondary module or field links.
Q: What power input is required to operate the CC-PFB401 module?
A: The module requires a nominal power supply of 24 VDC at a current draw of 210 mA from the backplane IOTA assembly.
Q: How many total fieldbus devices can a single CC-PFB401 module manage?
A: Each of the 4 H1 networks supports up to 16 fieldbus devices, enabling a single module to interface up to 64 field devices.
Field Installation Guidelines
- Mount the CC-PFB401 firmly onto the matching Series C IOTA carrier board until the locking latches fully engage the backplane connector.
- Verify that fieldbus segment shielding is properly grounded at the cabinet entry point to prevent common-mode noise on the 31.25 kbps H1 networks.
- Confirm that each of the four H1 segments has exactly two bus terminators installed at the physical ends of the trunk line.
- Maintain proper vertical cabinet ventilation paths to prevent thermal buildup around the conformally coated housing.