Honeywell CC-PWRB01 Series C Power Supply Card
Specifications
Manufacturer: Honeywell
Product No.: CC-PWRB01
Condition: 10 العناصر الموجودة في المخزون
Product Type: Power Supply Modules
Product Origin: USA
Payment:T/T, Western Union
Weight: 3000g
Shipping port: Xiamen
Warranty: 12 months
تفاصيل المنتج
وصف
The Honeywell CC-PWRB01, also cataloged as the CC-PWRB01 Power Supply Card, operates as a dedicated hardware component for 24 VDC power generation and system bus distribution within Honeywell Experion PKS C300 platforms. It converts 120/240 VAC mains input into regulated direct current to energize controller processors, backplane buses, and associated I/O modules.
Hardware Specifications
| Parameter | Specification |
|---|---|
| Model | CC-PWRB01 |
| Brand | Honeywell |
| Origin | USA |
| Weight | 3 kg (shipping weight) |
| Operating Temp | Standard industrial operating range |
| Power Consumption | 120/240 VAC input; 145 watts heat dissipation |
| Power Rating | 20 A power system capacity |
| Redundancy | Dual power supply redundant architecture |
| Backup Power | 24 V backup battery assembly support |
Galvanic Isolation & Power Bus Conditioning
The Honeywell CC-PWRB01 incorporates internal transformer galvanic isolation barriers between the high-voltage AC utility input and the low-voltage 24 VDC output bus. The power architecture features integrated ripple filtering, over-voltage clamping, and over-current trip protection to prevent mains transients from propagating into sensitive controller logic. Designed for redundant operation, dual CC-PWRB01 units connect in a diode-ORed configuration to support seamless load sharing and power bus continuity without voltage drops or backplane disruption during a single AC feed loss.
Frequently Asked Questions
Q: Does the CC-PWRB01 power supply card support hot-swapping during system operation?
A: Yes, in a redundant dual power supply configuration, a faulty CC-PWRB01 card can be removed and replaced under live AC power without interrupting the 24 VDC power delivery to the C300 controller rack.
Q: How is the secondary power source maintained if primary 120/240 VAC mains power fails?
A: The system automatically transitions power draw to the attached 24 V backup battery assembly without switching latency, maintaining continuous operational voltage across the backplane bus.
Q: What mechanism prevents power supply thermal overload inside closed cabinets?
A: The module is engineered for passive heat dissipation up to 145 watts; thermal monitoring circuits flag fault diagnostics to the C300 system if internal component temperatures exceed safe operating thresholds.
Field Installation Guidelines
- Verify that the incoming AC supply voltage matches the specified 120/240 VAC range before connecting power leads to the power distribution assembly.
- Align the card edge and heavy-current connectors of the CC-PWRB01 with the designated power slot card guides in the C300 rack.
- Slide the card firmly into place until the multi-pin backplane power connectors fully seat and the mechanical retention latches engage.
- Ensure the 24 V backup battery assembly connections are correctly wired with solid polarity orientation at the terminal blocks.
- Connect cabinet protective earth (PE) ground directly to the dedicated chassis grounding lug to ensure effective transient surge protection and noise immunity.