Honeywell Experion PKS C300 HART Analog Input Module | CC-PAIH02
Specifications
Manufacturer: Honeywell
Product No.: CC-PAIH02 51405038-175
Condition: 10 العناصر الموجودة في المخزون
Product Type: Analog Input Modules
Product Origin: USA
Payment:T/T, Western Union
Weight: 2000g
Shipping port: Xiamen
Warranty: 12 months
تفاصيل المنتج
وصف
Configured for high-density current and voltage signal processing in Experion PKS C300 systems, the Honeywell CC-PAIH02 (CC-PAIH02 HART Analog Input Module) provides direct physical/electrical execution.
Hardware Specifications
| Parameter | Specification |
|---|---|
| Model | CC-PAIH02 |
| Brand | Honeywell |
| Origin | USA |
| Weight | 2 kg (shipping weight) |
| Dimensions | Standard C300 I/O Module Dimensions |
| Operating Temp | -40 to +70 deg C |
| Power Consumption | 60 W |
| Product Type | HART Analog Input Module |
| Input Channels | 16 channels |
| Input Signal Types | 4-20 mA, 1-5 V, 0-5 V |
| Input Configuration | Differential / Single-ended analog input |
4-20 mA HART Loop Protocol and Channel-to-Channel Isolation
The Honeywell CC-PAIH02 processes up to 16 configurable differential or single-ended analog input channels across 4-20 mA, 1-5 V, and 0-5 V signal ranges. Operating over standard 4-20 mA HART loop protocol architectures, internal signal processing logic decouples field sensor circuits through dedicated channel-to-channel isolation networks. This electrical boundary prevents common-mode voltage spikes and ground loop currents from propagating into the core C300 controller backplane bus.
Frequently Asked Questions
Q: Does the CC-PAIH02 support online insertion and removal under live backplane power?
A: Yes, the module supports live hot-swapping on an active C300 carrier assembly without disrupting adjacent I/O channel execution or requiring a controller restart.
Q: How are differential and single-ended input modes selected on the module?
A: Input configuration modes for 4-20 mA, 1-5 V, and 0-5 V ranges are software-defined within the Experion PKS Control Builder environment on a per-channel basis.
Q: Can the module pass HART diagnostic variables directly to asset management tools?
A: Yes, the onboard HART modem extracts primary, secondary, tertiary, and quaternary dynamic variables from the 4-20 mA analog loop for transmission over the backplane.
Field Installation Guidelines
- Mount the module chassis onto the designated slot of the C300 IOTA carrier board, pressing firmly until the retention clips lock into position.
- Route 4-20 mA and low-voltage DC analog signal lines through dedicated wireways separated from AC power cables by at least 200 mm.
- Terminate shielded signal cable drain wires at a single common ground bus bar inside the cabinet to eliminate ground loops.
- Verify loop power voltage levels and field device polarity prior to energizing input channels.
- Maintain a minimum vertical clearance of 100 mm above and below the module assembly to ensure unobstructed convective cooling airflow.
كيفية الحصول على عرض أسعار