Honeywell MC-TAOX12 51304441-175 Analog Output FTA
Specifications
Manufacturer: Honeywell
Product No.: MU/MC-TAOX12 51304441-175
Condition: 10 العناصر الموجودة في المخزون
Product Type: Analog Output Modules
Product Origin: USA
Payment:T/T, Western Union
Weight: 500g
Shipping port: Xiamen
Warranty: 12 months
تفاصيل المنتج
وصف
The Honeywell 51304441-175, also cataloged as the MC-TAOX12 Analog Output Field Termination Assembly (FTA), operates as a dedicated hardware component for multi-channel process signal distribution within Honeywell HPM, TDC 3000, and Experion PKS platforms. Configured for driving 16 independent 4-20 mA current loops, the assembly routes analog control commands from redundant I/O processors to field actuators, control valves, and I/P transducers. The hardware utilizes multi-layer PCB construction with protective coating and compression-style screw terminals to maintain analog signal fidelity across extended field cable runs.
Hardware Specifications
| Parameter | Specification |
|---|---|
| Model | MC-TAOX12 (51304441-175) |
| Brand | Honeywell |
| Origin | USA |
| Operating Temp | 0 to 60 deg C |
| Power Consumption | 24 VDC Nominal |
| Part Number | 51304441-175 |
| Module Type | Analog Output Field Termination Assembly (FTA) |
| Channel Density | 16 Independent Channels |
| Signal Range | 4-20 mA DC |
| System Compatibility | Honeywell HPM / TDC 3000 / Experion PKS |
| Redundancy | Dual I/O Processor Connection Support |
| Termination | Compression-Style Screw Terminals |
4-20 mA HART Loop Protocol & Redundant Processor Interfacing
The Honeywell MC-TAOX12 51304441-175 incorporates dual-path signal routing architecture to interface directly with primary and secondary I/O processors. During processor failover, the board maintains seamless 4-20 mA current output delivery without signal dropping or transient spikes. The precision resistive networks integrated into each of the 16 channels ensure signal accuracy for 4-20 mA HART loop protocol field devices while isolating controller backplane logic from field-induced electrical noise.
Frequently Asked Questions
Q: How does the MC-TAOX12 handle processor redundancy during a failover event?
A: The FTA features dual-connector headers that interface simultaneously with primary and backup I/O processors, allowing passive hardware switching of the 4-20 mA command signal without interrupting loop power or signal continuity.
Q: What type of wiring connection is supported on the field side of the 51304441-175 assembly?
A: The board is equipped with heavy-duty compression-style screw terminals designed to accept stranded or solid copper field wiring directly for all 16 analog channels.
Q: Can the MC-TAOX12 FTA be powered directly from an external 24 VDC source?
A: Yes, nominal 24 VDC supply voltage can be supplied either through the primary I/O link interface cable or via dedicated external 24 VDC power distribution terminals.
Field Installation Guidelines
- De-energize all 24 VDC power sources and disconnect field load wiring before installing or replacing the FTA board in the enclosure rack.
- Secure the 6-inch assembly onto the cabinet mounting channel, ensuring metallic grounding clips make firm, low-resistance contact with the chassis earth rail.
- Attach the dual I/O interface cables from the main and redundant High-Performance Process Manager (HPM) or Experion I/O card racks to the FTA headers.
- Strip field conductor insulation to the recommended length and secure wires into the compression screw terminals, observing correct positive and negative loop polarity per channel.
- Ensure overall cable shielding is grounded at a single designated cabinet earth point to prevent ground loop currents from interfering with 4-20 mA analog outputs.