Honeywell RM7895A1014/U Burner Mod Primary Control

Specifications

  • Manufacturer: Honeywell

  • Product No.: RM7895A1014/U

  • Condition: 10 العناصر الموجودة في المخزون

  • Product Type: Burner Primary Controls

  • Product Origin: USA

  • Payment:T/T, Western Union

  • Weight: 2000g

  • Shipping port: Xiamen

  • Warranty: 12 months

تفاصيل المنتج

وصف

The RM7895A1014/U is a microprocessor-based integrated primary burner control engineered by Honeywell for automatically fired gas, oil, or combination-fuel single burner applications. This unit provides on-off primary control with integrated prepurge functionality, delivering advanced safety, functional capability, and system diagnostics compared to conventional controls. Key functions include automatic burner sequencing, flame supervision, airflow switch checks, and comprehensive nonvolatile memory for history retention.

System Architecture and Required Components

Operation of this primary control requires specific plug-in components, including a Q7800A or Q7800B universal wiring subbase, an interchangeable plug-in flame amplifier compatible with the 7800 Series, and an ST7800A plug-in purge timer card to determine prepurge timing. Five diagnostic LEDs provide real-time sequence information, while nonvolatile memory retains history files and sequencing status even after a power loss.

Electrical Ratings and Environmental Performance

The control operates on a 120 Vac supply voltage at 50 Hz or 60 Hz frequencies with a ±10% tolerance. It is housed in an enclosure designed to withstand a 0.5 G vibration environment and supports a shipping and storage temperature range of -40 deg C to +60 deg C. The unit carries recognized and certified industrial approvals including UL, CSA, Factory Mutual, and CSD-1 compliance.

Technical Specifications

Parameter Specification
Model RM7895A1014/U
Brand Honeywell
Product Type Burner Mod Primary Control (On-Off Primary Control with Prepurge)
Voltage 120 Vac (+10, -15%)
Frequency 50 Hz / 60 Hz (±10%)
Flame Establishing Period - Pilot 4 sec or 10 sec
Flame Establishing Period - Main Intermittent
Required Components Q7800A/B Subbase, 7800 Series Flame Amplifier, ST7800A Purge Timer Card
Used With 7800 Series Amplifiers
Dimensions (with Q7800A Subbase) 127 mm x 127 mm x 133 mm (5 in. x 5 in. x 5 1/4 in.)
Dimensions (with Q7800B Subbase) 127 mm x 127 mm x 155 mm (5 in. x 5 in. x 6 3/32 in.)
Operating/Storage Temperature -40 deg C to +60 deg C (-40 F to +140 F)
Vibration Tolerance 0.5 G environment
Weight 0.9 kg (1 lb 15 oz)
Shipping Weight 2 kg
Approvals UL File No. MP268, CSA File No. LR95329-3, FM Report No. OX4A5.AF, CSD-1, Swiss RE, FCC Part 15 Class B

Frequently Asked Questions

Q: What mandatory plug-in components are required for the RM7895A1014/U to operate?

A: It requires a Q7800A or Q7800B universal wiring subbase, a compatible 7800 Series plug-in flame amplifier, and an ST7800A purge timer card.

Q: How does the control retain data during a power interruption?

A: It features built-in nonvolatile memory that retains historical error files and sequencing status after a power loss.

Q: What is the nominal operating voltage for this primary burner control? A: It operates on 120 Vac power at 50 Hz or 60 Hz frequencies.