Honeywell TC-FIAH81 8-Channel High-Level Analog Input Module
Specifications
Manufacturer: Honeywell
Product No.: TC-FIAH81
Condition: 10 العناصر الموجودة في المخزون
Product Type: Analog Input Modules
Product Origin: USA
Payment:T/T, Western Union
Weight: 220g
Shipping port: Xiamen
Warranty: 12 months
تفاصيل المنتج
وصف
The Honeywell TC-FIAH81, also cataloged as the TC-FIAH81 High-Level Analog Input Module, operates as a dedicated hardware component for high-level signal acquisition within Experion PKS, TDC 3000, and C200 controller platforms. The module accepts up to 8 single-ended input channels, digitizing process variables into internal system memory. Internal signal conditioning converts field voltage and current inputs into 12-bit digital values while providing galvanic isolation between system backplane logic and field-side wiring.
Hardware Specifications
| Parameter | Specification |
|---|---|
| Model | TC-FIAH81 |
| Brand | Honeywell |
| Origin | USA |
| Weight | 0.11 kg (Unit) / 0.22 kg (Shipping) |
| Dimensions | 105 x 115 x 90 mm |
| Operating Temp | 0 to 60 deg C |
| Power Consumption | 3 W Maximum at 31.2 VDC |
| Backplane Current | 15 mA at 5 VDC, 60 mA at 24 VDC |
| Channels | 8 Single-ended Inputs |
| Voltage Input Range | +/-10 V, 0 to 10 V |
| Current Input Range | 4-20 mA, 0-20 mA |
| Analog Resolution | 12 bits (Unipolar); 11 bits + sign (Bipolar) |
| Input Impedance | Voltage: 100 kOhm; Current: 238 Ohm |
| Isolation Rating | 850 VDC for 1 second (User-to-System) |
| Thermal Dissipation | 10.2 BTU/hr |
4-20 mA HART Loop Protocol & Channel-to-Channel Isolation
The Honeywell TC-FIAH81 incorporates an internal 238 Ohm precision resistor circuit to execute accurate current-to-voltage conversion for standard 4-20 mA loop protocols. User-to-system galvanic isolation rated at 850 VDC protects backplane electronics from field-side transients and ground potential differentials. Each channel allows independent parameter configuration via control software, preventing signal distortion and ground-loop propagation across adjacent 0 to 10 V or 4-20 mA measurement loops.
Frequently Asked Questions
Q: Does the TC-FIAH81 module require external power to drive 4-20 mA loop transmitters?
A: Logic power (5 VDC and 24 VDC) is supplied via the FlexBus backplane. External field power is required for 2-wire transmitters depending on system loop architecture, whereas the module directly conditions incoming loop current through its internal 238 Ohm impedance path.
Q: Can voltage and current input modes be configured simultaneously on a single module?
A: Yes, each of the 8 single-ended channels can be independently configured for either voltage (+/-10 V, 0 to 10 V) or current (4-20 mA, 0-20 mA) in the software environment without cross-channel interference.
Q: How does backplane power consumption affect cabinet thermal design?
A: The module draws 15 mA at 5 VDC and 60 mA at 24 VDC from the FlexBus, generating a maximum power dissipation of 3 W and a thermal output of 10.2 BTU/hr, which must be factored into cabinet heat dissipation limits.
Field Installation Guidelines
- Align the TC-FIAH81 module with the chassis guide rails in the C200 or Experion I/O rack.
- Slide the unit inward until the rear connectors fully seat into the FlexBus backplane to establish power and communication paths.
- Verify that channel signal types (voltage or current) selected in Experion Control Builder match the physical field wiring configuration prior to applying loop power.
- Use shielded twisted-pair (STP) cabling for all analog input runs to minimize external electromagnetic noise interference.
- Terminate overall cable shields at a single point on the system earth ground bus to avoid loop current ground shifts.