Honeywell TC-IAH061 96978074-A01 Experion Analog Input Module
Specifications
Manufacturer: Honeywell
Product No.: TC-IAH061 96978074-A01
Condition: 10 العناصر الموجودة في المخزون
Product Type: Analog Input Modules
Product Origin: USA
Payment:T/T, Western Union
Weight: 2500g
Shipping port: Xiamen
Warranty: 12 months
تفاصيل المنتج
وصف
The Honeywell TC-IAH061 96978074-A01, also cataloged as the TC-IAH061 Analog Input Modules, operates as a dedicated hardware component for high-speed multi-channel field variable acquisition within Experion PKS C200/C300 controller chassis platforms.
Hardware Specifications
| Parameter | Specification |
|---|---|
| Model | TC-IAH061 (Part Number: 96978074-A01) |
| Brand | Honeywell |
| Origin | USA |
| Weight | 2.5 kg (Shipping Weight) |
| Dimensions | Standard Experion C200/C300 module enclosure |
| Operating Temp | 0 to +60 deg C housing thermal envelope |
| Power Dissipation | 4.3 W max |
| Channel Capacity | 6 galvanically isolated channels |
| Channel Bandwidth | 0 to 15 Hz (-3 dB) |
| Module Update Rate | 25 ms across all channels |
| Open Circuit Detection | Upscale reading (Voltage); Zero scale reading (Current) |
| OC Detection Time | 5 seconds (Voltage); 1 second (Current) |
| RFI Immunity | Error less than 2.0% of range at 10 V/m (27 to 1000 MHz) |
| Terminal Assembly | TC-TBNH 20-position terminal block |
| Product Category | Analog Input Modules |
Channel-to-Channel Isolation & 4-20 mA HART Loop Protocol Execution
The TC-IAH061 module incorporates internal optical barriers providing full channel-to-channel isolation across all 6 analog input channels. Designed to process differential 4-20 mA HART loop protocol and voltage signals, the hardware suppresses common-mode noise and prevents ground loop currents between field devices. Integrated signal-conditioning circuits execute open-circuit detection while maintaining a 25 ms update rate across all channels and filtering RF interference to less than 2.0% error under 10 V/m field exposure.
Frequently Asked Questions
Q: Does replacing a TC-IAH061 module require disconnecting field wiring from the terminal assembly?
A: No, field wiring lands directly on the 20-position TC-TBNH terminal block, allowing the active TC-IAH061 module to be unseated while field conductors stay attached.
Q: How does the TC-IAH061 handle open circuit conditions on current loops versus voltage inputs?
A: Open circuit detection yields a zero-scale reading for current inputs within 1 second, whereas voltage inputs drive to an upscale reading within 5 seconds.
Q: Can the TC-IAH061 module be hot-swapped during active controller operation?
A: Hot-swapping is supported when installed in compatible backplane racks, subject to site safety rules and cabinet hazardous area classifications.
Field Installation Guidelines
- Seat the TC-IAH061 module into the designated slot on the chassis rack until the mounting levers snap into the locked position.
- Align the 20-position TC-TBNH terminal block with the module header pins and press firmly to secure mechanical engagement.
- Terminate shielded twisted-pair signal cables to the TC-TBNH screw terminals, maintaining proper wire gauge and strip dimensions.
- Ground all cable drain shields directly to the cabinet enclosure earth ground bar to maintain specified RFI immunity performance.