Honeywell TC-ODK161 AC Digital Output Module

Specifications

  • Manufacturer: Honeywell

  • Product No.: TC-ODK161

  • Condition: 10 العناصر الموجودة في المخزون

  • Product Type: Digital Output Cards

  • Product Origin: USA

  • Payment:T/T, Western Union

  • Weight: 290g

  • Shipping port: Xiamen

  • Warranty: 12 months

تفاصيل المنتج

وصف

The Honeywell TC-ODK161, also cataloged as the TC-ODK161 AC Digital Output Module, operates as a dedicated hardware component for switching high-voltage AC field discrete devices across Honeywell DCS platforms.

Hardware Specifications

Parameter Specification
Model TC-ODK161
Brand Honeywell
Origin USA
Weight 0.29 kg
Dimensions Standard Rack Form Factor
Operating Temp 0 to +60 deg C
Power Consumption System Backplane Driven
Output Voltage Range 120/220 VAC
Channel Density 16 Points
Line Frequency 50/60 Hz
Maximum Output Current 2 A per point
Revision Level Rev G0

Channel-to-Channel Isolation and Loop Diagnostics

The TC-ODK161 incorporates internal optical isolation barriers between backplane logic circuitry and field-side switching elements. Channel-to-channel isolation suppresses inductive kickback transients and ground loops originating from solenoid valves, motor starters, or AC actuators. This electrical isolation prevents field-side AC interference from propagating to adjacent analog processing racks carrying sensitive 4-20 mA HART loop communication networks or precision measurement logic.

Frequently Asked Questions

Q: What is the maximum AC load current capacity per output point on the TC-ODK161?

A: Each individual output point on the TC-ODK161 module supports a maximum continuous load current of 2 A at 120/220 VAC (50/60 Hz).

Q: Does inserting or removing the TC-ODK161 require shutting down system backplane power?

A: Hot-swapping must strictly conform to system chassis guidelines; verify that field-side 120/220 VAC power distribution circuits are isolated before removing or inserting the module to prevent electrical arcing across backplane pins.

Field Installation Guidelines

  • Isolate all external 120/220 VAC field power sources prior to connecting or disconnecting wiring harnesses from the terminal block assembly.
  • Maintain clear physical separation between AC high-voltage output wiring and low-voltage analog signal cables to prevent inductive noise coupling.
  • Secure the module chassis firmly into the backplane slot, ensuring positive engagement of retaining clips to verify proper earth ground continuity.
  • Connect field cable shields to the dedicated cabinet single-point ground bar to minimize electromagnetic interference across control channels.
  • Verify total current load per output group to ensure thermal limits within the control enclosure are not exceeded.

كيفية الحصول على عرض أسعار

تتبع الطلب

شركات الشحن

سياسة وشروط الاسترداد

شروط الضمان

منتجات ذات صله