Honeywell TC-PRR021 Redundancy Power Regulator Module
Specifications
Manufacturer: Honeywell
Product No.: TC-PRR021 51309288-225
Condition: 10 العناصر الموجودة في المخزون
Product Type: Power Regulator Modules
Product Origin: USA
Payment:T/T, Western Union
Weight: 300g
Shipping port: Xiamen
Warranty: 12 months
تفاصيل المنتج
وصف
The Honeywell TC-PRR021, also cataloged as the 51309288-225 Redundant Power Regulator Module, operates as a dedicated hardware component for dual-input power redundancy and 24 VDC bus stabilization within Honeywell Experion PKS and TDC 3000 platforms.
Hardware Specifications
| Parameter | Specification |
|---|---|
| Model | TC-PRR021 |
| Brand | Honeywell |
| Part Number | 51309288-225 |
| Origin | USA |
| Weight | 1.5 kg |
| Dimensions | 180 x 100 x 25 mm |
| Operating Temp | -25 to +70 deg C |
| Power Consumption | Universal Input: 85-265 VAC; Output: 24 VDC Regulated |
| Humidity Limits | 5% to 95% Non-condensing |
| System Compatibility | Honeywell Experion PKS, TDC 3000 |
| Circuit Protection | Overload, Short-circuit, and Thermal protection |
| Compliance Certifications | CE, UL, CSA Industrial Compliance |
4-20 mA HART Loop and Channel Isolation Features
The TC-PRR021 integrates directly into Experion PKS backplane topologies to deliver continuous power bus isolation across industrial controller racks and I/O channels. By maintaining strict voltage regulation under heavy system loads, the unit eliminates power-line ripple that could otherwise introduce noise onto sensitive 4-20 mA HART communication loops. Integrated protective diode networks enforce channel-to-channel power isolation, preventing a field side short circuit or field wiring fault from propagating to adjacent controller nodes or disturbing analog signal processing logic.
Frequently Asked Questions
Q: What is the transfer time behavior during a primary power source interruption?
A: The switchover execution within the unit operates seamlessly. Output voltage stability is maintained across the dual-input diode switch circuitry without voltage dropouts, preventing controller resets or signal dropouts on downstream I/O modules.
Q: Does the unit support wide-range AC power distribution without external tap switches?
A: Yes. The internal power stage accepts an input range of 85 to 265 VAC, accommodating global line voltages without manual transformer reconfiguration or external jumper selection.
Field Installation Guidelines
- Verify that the chassis power rail is fully de-energized or operating under approved hot-swap procedures before inserting the module into the standard Honeywell power rack frame.
- Ensure positive mechanical seating of the module backplane connector into the rack receptacle to secure optimal electrical contact and low-resistance grounding paths.
- Connect primary and secondary power feeds from distinct, galvanically isolated power sources to achieve true fault-tolerant electrical redundancy.
- Maintain at least 50 mm of unobstructed vertical clearance above and below the module enclosure within the control cabinet to facilitate natural convection cooling and prevent localized thermal build-up.
- Ground all field cable shields strictly at the designated cabinet single-point ground bar to mitigate common-mode noise propagation to the power backplane.