MC-PSRX04 51198947-100K Honeywell Power System Housing
Specifications
Manufacturer: Honeywell
Product No.: MC-PSRX04 51198947-100K
Condition: 10 العناصر الموجودة في المخزون
Product Type: Power Supply Modules
Product Origin: USA
Payment:T/T, Western Union
Weight: 600g
Shipping port: Xiamen
Warranty: 12 months
تفاصيل المنتج
وصف
Configured for centralized power distribution in Honeywell Distributed Control System platforms, the Honeywell 51198947-100K (MC-PSRX04 Power System Housing) provides direct physical/electrical execution.
Hardware Specifications
| Parameter | Specification |
|---|---|
| Model | MC-PSRX04 51198947-100K |
| Brand | Honeywell |
| Origin | USA |
| Weight | 0.6 kg |
| Dimensions | Standard Honeywell Rack Footprint (Thickness: 2.2 cm) |
| Operating Temp | 0 to 60 deg C |
| Power Consumption | Input: 115 VAC, Total Output: 0.565 kW |
| Output Current Ratings | 20 A / 1 A / 0.035 A |
| I/O Processor Capacity | Up to 40 Processors (Redundant or Non-Redundant) |
| Redundancy Support | One-on-one I/O Redundancy |
| Signal Compatibility | Analog I/O, Digital I/O, Smart Transmitters |
| Backplane Protection | Conformal Coating (CC) |
Process Control & Channel Isolation
The MC-PSRX04 Power System Housing distributes regulated power lines across backplane buses to drive digital, analog, and smart transmitter interface cards. Fully compatible with 4-20 mA HART loop protocol architectures, the backplane integrates robust channel-to-channel isolation and galvanic protection circuit paths. The conformally coated assembly protects copper traces against industrial atmospheric contaminants, preventing ground loops and common-mode noise propagation between redundant I/O processor channels.
Frequently Asked Questions
Q: How many I/O processors can be installed within a single MC-PSRX04 housing assembly?
A: The housing supports up to 40 redundant or non-redundant I/O processors across its backplane slots.
Q: What input and output power specifications govern the MC-PSRX04 backplane distribution?
A: The housing accepts a nominal 115 VAC input and provides a total output power capacity of 0.565 kW with DC current rails rated at 20 A, 1 A, and 0.035 A.
Q: How does conformal coating protect the backplane circuit board in harsh plant environments?
A: Conformal coating applies a protective polymer layer over the printed circuit assembly, preventing moisture, chemical gases, and particulate matter from causing corrosion or parasitic electrical leakage.
Field Installation Guidelines
- Disconnect all 115 VAC primary power sources before mounting or servicing the MC-PSRX04 chassis.
- Confirm that the housing is bonded securely to the cabinet grounding bus using heavy-gauge earth grounding straps to suppress electrical noise.
- Ensure adequate vertical airflow spacing above and below the chassis assembly to maintain thermal dissipation across full 0.565 kW load profiles.
- Verify that all processor card edge connectors are aligned correctly before fully seating modules into backplane slots.
كيفية الحصول على عرض أسعار