{"product_id":"r7861a1026-honeywell-flame-amplifier","title":"R7861A1026 | Honeywell | Flame Amplifier","description":"\u003cp\u003eThe Honeywell \u003cstrong\u003eR7861A1026\u003c\/strong\u003e is a dynamic self-checking ultraviolet flame amplifier designed to plug into Honeywell 7800 Series relay modules. It monitors flame detector inputs to verify the presence of combustion, providing flame failure response times of 2.0 or 3.0 seconds while executing continuous self-checks on both system electronics and connected detectors.\u003c\/p\u003e\n\u003ch3\u003eFunctionality and Signal Monitoring\u003c\/h3\u003e\n\u003cp\u003eThis solid-state plug-in module interfaces with 7800 Series relay modules via a keyed printed circuit board edge connector for correct orientation. It features integrated flame signal test jacks that allow technicians to measure amplifier DC voltage ranging from 0.0 to 5.0 Vdc. The purple color-coded label identifies its specific dynamic self-check ultraviolet detection type, triggering a safety shutdown if any component or detector failure occurs.\u003c\/p\u003e\n\u003ch3\u003eSystem Compatibility\u003c\/h3\u003e\n\u003cp\u003eThe amplifier is specifically engineered for use with Honeywell C7061 ultraviolet flame sensors across gas, oil, or coal burner applications. It operates in conjunction with 7800 Series primary safety control relay modules to maintain reliable flame supervision and safety interlocks.\u003c\/p\u003e\n\u003cfigure class=\"table\"\u003e\n\u003ctable\u003e\n\u003cthead\u003e\n\u003ctr\u003e\n\u003cth\u003e\u003cstrong\u003eParameter\u003c\/strong\u003e\u003c\/th\u003e\n\u003cth\u003e\u003cstrong\u003eSpecification\u003c\/strong\u003e\u003c\/th\u003e\n\u003c\/tr\u003e\n\u003c\/thead\u003e\n\u003ctbody\u003e\n\u003ctr\u003e\n\u003ctd\u003eModel\u003c\/td\u003e\n\u003ctd\u003eR7861A1026\u003c\/td\u003e\n\u003c\/tr\u003e\n\u003ctr\u003e\n\u003ctd\u003eBrand\u003c\/td\u003e\n\u003ctd\u003eHoneywell\u003c\/td\u003e\n\u003c\/tr\u003e\n\u003ctr\u003e\n\u003ctd\u003eProduct Type\u003c\/td\u003e\n\u003ctd\u003eFlame Amplifier\u003c\/td\u003e\n\u003c\/tr\u003e\n\u003ctr\u003e\n\u003ctd\u003eFlame Detection Type\u003c\/td\u003e\n\u003ctd\u003eDynamic Self-Check Ultraviolet (UV)\u003c\/td\u003e\n\u003c\/tr\u003e\n\u003ctr\u003e\n\u003ctd\u003eFlame Failure Response Time\u003c\/td\u003e\n\u003ctd\u003e2.0 sec or 3.0 sec\u003c\/td\u003e\n\u003c\/tr\u003e\n\u003ctr\u003e\n\u003ctd\u003eFlame Signal Voltage Range\u003c\/td\u003e\n\u003ctd\u003e0.0 to 5.0 Vdc\u003c\/td\u003e\n\u003c\/tr\u003e\n\u003ctr\u003e\n\u003ctd\u003eColor Code\u003c\/td\u003e\n\u003ctd\u003ePurple\u003c\/td\u003e\n\u003c\/tr\u003e\n\u003ctr\u003e\n\u003ctd\u003eCompatible Flame Sensor\u003c\/td\u003e\n\u003ctd\u003eC7061 Ultraviolet Flame Sensor\u003c\/td\u003e\n\u003c\/tr\u003e\n\u003ctr\u003e\n\u003ctd\u003eCompatible Relay Modules\u003c\/td\u003e\n\u003ctd\u003eHoneywell 7800 Series Relay Modules\u003c\/td\u003e\n\u003c\/tr\u003e\n\u003ctr\u003e\n\u003ctd\u003eShipping Weight\u003c\/td\u003e\n\u003ctd\u003e2 kg\u003c\/td\u003e\n\u003c\/tr\u003e\n\u003c\/tbody\u003e\n\u003c\/table\u003e\n\u003c\/figure\u003e\n\u003cp\u003eFrequently Asked Questions\u003c\/p\u003e\n\u003cp\u003eQ: What flame sensors are compatible with the R7861A1026 amplifier?\u003c\/p\u003e\n\u003cp\u003eA: It is designed to work with Honeywell C7061 ultraviolet flame sensors used in gas, oil, or coal burner applications.\u003c\/p\u003e\n\u003cp\u003eQ: How is the flame signal voltage measured during operation?\u003c\/p\u003e\n\u003cp\u003eA: Flame signal voltage can be measured directly using the integrated amplifier test jacks, yielding a reading between 0.0 and 5.0 Vdc.\u003c\/p\u003e","brand":"Honeywell","offers":[{"title":"Default Title","offer_id":68170429530408,"sku":"R7861A1026","price":315.0,"currency_code":"USD","in_stock":true}],"thumbnail_url":"\/\/cdn.shopify.com\/s\/files\/1\/0827\/6266\/2184\/files\/R7861A10261.png?v=1794475170","url":"https:\/\/www.powerdcs.com\/ar\/products\/r7861a1026-honeywell-flame-amplifier","provider":"Power DCS Parts Limited","version":"1.0","type":"link"}