RM7823A1016/U Flame Switch Relay | Honeywell
Specifications
Manufacturer: Honeywell
Product No.: RM7823A1016/U
Condition: 10 العناصر الموجودة في المخزون
Product Type: Flame Detector Relays
Product Origin: USA
Payment:T/T, Western Union
Weight: 5000g
Shipping port: Xiamen
Warranty: 12 months
تفاصيل المنتج
وصف
The RM7823A1016/U is a microprocessor-based integrated flame switch designed to detect burner flames using rectification, ultraviolet (UV), or infrared (IR) sources. It functions strictly as a flame detector relay featuring two single-pole, double-throw (SPDT) relay outputs, requiring a suitable primary control to handle safe-start checks, safety lockouts, and load switching.
System Compatibility and Architecture
Compatible with any 7800 Series amplifier and existing Honeywell flame detectors, the unit provides relay action depending on flame presence. It incorporates dynamic self-check logic and Dynamic AMPLI-CHECK circuitry, offering interchangeable plug-in flame amplifiers that yield either 0.8 or 3.0 seconds of flame failure response time (FFRT).
Diagnostics and Data Logging
The controller features three status LEDs for power, flame, and alarm indications, alongside nonvolatile memory that retains history files and fault logs during power loss. Optional diagnostics via an optional Keyboard Display Module provide burner controller data, including flame signal strength, operating hours and cycles, and fault history logs.
Technical Parameters
| Parameter | Specification |
|---|---|
| Model | RM7823A1016/U |
| Brand | Honeywell |
| Product Type | Flame Switch Relay |
| Output Configuration | Two SPDT outputs (relay action for flame present / not present) |
| Voltage | 120 VAC |
| Frequency | 50 / 60 Hz |
| Flame Failure Response Time (FFRT) | 0.8 s or 3.0 s (depending on amplifier selected) |
| Safety Features | Dynamic self-check logic, Dynamic AMPLI-CHECK, tamper-resistant logic |
| Diagnostics & Status | Three status LEDs (power, flame, alarm); optional VFD Keyboard Display Module |
| Memory | Nonvolatile memory for history files and fault status retention |
Frequently Asked Questions
Q: What primary functions does the Honeywell RM7823A1016/U perform in a burner system?
A: It acts as an integrated flame detector relay providing two SPDT outputs, but requires a separate primary control to execute safety lockouts, safe-start checks, and load switching.
Q: How is the flame failure response time determined for this unit?
A: The FFRT is either 0.8 or 3.0 seconds, depending on the specific plug-in flame amplifier selected for the installation.
كيفية الحصول على عرض أسعار
تتبع الطلب
شركات الشحن
سياسة وشروط الاسترداد