TC-OAV061 REV K01 Analog Output Module | Honeywell
Specifications
Manufacturer: Honeywell
Product No.: TC-OAV061
Condition: 10 العناصر الموجودة في المخزون
Product Type: Analog Output Modules
Product Origin: USA
Payment:T/T, Western Union
Weight: 280g
Shipping port: Xiamen
Warranty: 12 months
تفاصيل المنتج
وصف
Configured for high-precision analog signal generation in Experion PKS C200/C300 rack systems, the Honeywell TC-OAV061 REV K01 (TC-OAV061 Analog Output Modules) provides direct physical/electrical execution.
Hardware Specifications
| Parameter | Specification |
|---|---|
| Model | TC-OAV061 REV K01 (Catalog Base: TK-OAV061) |
| Brand | Honeywell |
| Origin | USA |
| Weight | 0.28 kg |
| Dimensions | 3.5 cm x 14.0 cm x 14.5 cm |
| Operating Temp | 0 to +60 deg C housing thermal envelope |
| Power Consumption | 100 mA at 24 VDC external supply |
| Channel Count | 6 isolated analog outputs |
| Output Range | 0 to 10 VDC |
| Max Output Current | 20 mA per channel |
| Conversion Performance | 12 bits resolution, 2 ms update time, +/-0.1% FS accuracy |
| Product Category | Analog Output Modules |
Channel-to-Channel Isolation & Signal Conditioning
The TC-OAV061 REV K01 converts internal digital control values into 6 galvanically isolated analog outputs across a 0 to 10 VDC range. Channel-to-channel isolation circuits prevent potential ground loop coupling and suppress transient field electrical interference from migrating into the backplane logic. The module maintains steady 12-bit D/A conversion accuracy (+/-0.1% FS) with a 2 ms update cycle, providing stable analog driving signals for field control devices while mitigating common-mode potential shifts.
Frequently Asked Questions
Q: Does replacing a TC-OAV061 REV K01 module require shutting down the main chassis rack power?
A: Module removal under power (hot-swapping) is permitted on compatible backplanes provided local cabinet hazardous area conditions and site safety practices allow it.
Q: How does channel-to-channel isolation on the TC-OAV061 REV K01 affect signal loop integrity?
A: Galvanic separation prevents field ground loops between individual output loops, protecting adjacent channels if a ground fault occurs on a single field line.
Q: What external supply is required to power the output circuitry on the TC-OAV061 REV K01?
A: The module relies on a nominal 24 VDC power supply drawer, consuming 100 mA under full operational load.
Field Installation Guidelines
- Slide the TC-OAV061 REV K01 module into the target rack chassis slot until the mechanical retention levers click securely into place.
- Route 0 to 10 VDC signal conductors using twisted, shielded cable pairs to minimize external electromagnetic interference.
- Connect signal cable shield drain wires to the central enclosure grounding bus at a single landing point.
- Verify correct terminal screw torque and wiring polarity before applying 24 VDC auxiliary loop power.