Triconex 3351 Analog Input Module
Specifications
Manufacturer: Triconex
Product No.: 3351
Condition: 10 العناصر الموجودة في المخزون
Product Type: Analog Input Modules
Product Origin: USA
Payment:T/T, Western Union
Weight: 1500g
Shipping port: Xiamen
Warranty: 12 months
تفاصيل المنتج
وصف
The Triconex 3351 is a 32-channel analog input module designed for high-integrity safety instrumented systems. It acquires 4-20 mA current signals from field transmitters and converts them for processing within Triple Modular Redundancy architectures, ensuring continuous signal monitoring and deterministic safety responses.
Channel Configuration and Measurement
The module supports 32 commoned input points with a nominal input range of 4-20 mA DC and an operational range spanning 2-22 mA DC. Signal conversion relies on a precision 100 ohm resistor with 0.01% accuracy, yielding a 12-bit resolution and an absolute error of 0.15% of full scale at 20 mA.
Performance and Diagnostics
Signal scanning for all 32 channels completes in less than 1 ms, supporting rapid fault detection in safety loops. The module incorporates force-to-value diagnostic functionality to verify input channel behavior under controlled test conditions, alongside built-in isolation between functional and protective grounds.
Technical Specifications
| Parameter | Specification |
|---|---|
| Model | 3351 |
| Brand | Triconex |
| Module Type | Analog Input Module |
| Channel Capacity | 32 points, commoned |
| Nominal Input | 4-20 mA DC |
| Operational Range | 2-22 mA DC |
| Resolution | 12 bits |
| Scan Time | <1 ms for all 32 points |
| Source Impedance | 180 ohm |
| Input Impedance | 250 ohm (with backplane) |
| Power Consumption | 3 W maximum logic power |
| Weight | ~1.5 kg |
Field Installation Guidelines
● Install the module in designated rack slots with full connector engagement.
● Ensure shielded cabling for 4-20 mA loops is grounded at a single point to avoid circulating currents.
● Route analog wiring separately from high-voltage conductors to minimize induced noise.
● Verify input excitation current and field voltage before energizing the module.
Frequently Asked Questions
Q: Can the 3351 module be hot-swapped during system operation? A: No. Power must be removed from the rack before insertion or removal to avoid backplane disruption.
Q: How fast does the module scan all channels? A: All 32 points are synchronously scanned in less than 1 ms.
Q: What diagnostic capability is provided? A: The module supports force-to-value diagnostics, allowing verification of input channel behavior under controlled conditions.
كيفية الحصول على عرض أسعار
تتبع الطلب
شركات الشحن
سياسة وشروط الاسترداد
شروط الضمان
منتجات ذات صله
- يؤدي اختيار تحديد إلى تحديث كامل للصفحة.