Specifications

  • Manufacturer: Honeywell

  • Product No.: XF821A

  • Condition: 10 العناصر الموجودة في المخزون

  • Product Type: Analog Input Modules

  • Payment:T/T, Western Union

  • Weight: 200g

  • Shipping port: Xiamen

  • Warranty: 12 months

تفاصيل المنتج

وصف

The Honeywell XF821A, also cataloged as the XF821A Panel Bus Analog Input Module, operates as a dedicated hardware component for resistive temperature signal acquisition within Excel 800 and CIPer 50 control systems. It executes physical signal conversion across 8 analog input channels, supporting multiple resistance temperature detector types without requiring complex external conditioning networks.

Hardware Specifications

Parameter Specification
Model XF821A
Brand Honeywell
Operating Temp 0 deg C to +50 deg C
Power Consumption 5 VA
Number of Inputs 8 analog inputs
Supported Sensors NTC10k, NTC20k, Ni1000, Pt1000, Pt3000
Supply Voltage 24 VAC/DC
Communication Interface Panel Bus
Certifications UL864 (UUKL) Smoke Control certified

Channel-to-Channel Isolation And Panel Bus Architecture

Operating within DCS and process control ecosystems, the module implements strict signal processing boundaries to maintain measurement fidelity. The Panel Bus interface handles deterministic data exchange with parent controllers, ensuring low-latency status reporting for temperature loops. Circuitry is designed to process resistive sensor inputs directly, reducing common-mode noise and stabilizing analog-to-digital conversion parameters in industrial building automation environments.

Frequently Asked Questions

Q: Does the XF821A support hot-swapping during active system operation?

A: Hot-swapping is restricted depending on the specific backplane power and controller configuration; power should be removed from the local node prior to module extraction or insertion to prevent bus communication faults.

Q: What is the primary communication protocol used to interface with the Excel 800 controller?

A: The module communicates via the proprietary Panel Bus interface, which provides synchronized data transfer and power distribution over a local multi-drop connection.

Field Installation Guidelines

  1. Mount the module securely onto a standard DIN rail inside a protective electrical enclosure.
  2. Ensure the 24 VAC/DC power supply is isolated and disconnected before wiring field terminals.
  3. Terminate shielded cables for resistive temperature sensors properly, ensuring the shield drain wire is grounded at a single, low-impedance earth point to mitigate electromagnetic interference.
  4. Verify all sensor connections against the pinout documentation for NTC10k, NTC20k, Ni1000, Pt1000, or Pt3000 types prior to system power-up.