8U-TDILB1 Honeywell Series 8 Digital Input Module

Specifications

  • Manufacturer: Honeywell

  • Product No.: 8U-TDILB1

  • Condition: 10 Artículos en stock

  • Product Type: Digital I/O Cards

  • Product Origin: USA

  • Payment:T/T, Western Union

  • Weight: 1100g

  • Shipping port: Xiamen

  • Warranty: 12 months

Detalles de producto

Descripción

The Honeywell 8U-TDILB1, also cataloged as the 8U-TDILB1 Digital Input Module, operates as a dedicated hardware component for high-speed discrete signal acquisition within Honeywell Experion PKS platforms.

Hardware Specifications

Parameter Specification
Model 8U-TDILB1
Brand Honeywell
Origin USA
Weight 0.55 lbs
Dimensions 4.75 x 3.5 x 1.5 inches
Operating Temp -20 deg C to +60 deg C
Power Consumption 95 mA module current rating
Input Channels 16 digital input channels
Voltage Rating 24 VDC nominal
DI Power Voltage Range 18 to 30 VDC
Response Time Less than 1 ms
Insulation Rating 600 V
Galvanic Isolation 1000 VAC RMS or +/-1500 VDC
ON State Threshold 13 VDC (min) or 3 mA (min)
OFF State Threshold 5 VDC (max) or 1.2 mA (max)
Input Impedance 4.2 k ohms

Process Control Input Signal Conditioning and Channel Isolation

The Honeywell 8U-TDILB1 processes 16 discrete field channels with an input impedance of 4.2 k ohms and a response time under 1 ms. Galvanic isolation rated at 1000 VAC RMS or +/-1500 VDC isolates field sensing loops from host system backplane logic, preventing transient voltage spikes and ground potential shifts from degrading digital state detection. The module evaluates 24 VDC field input states using fixed thresholds (ON state at 13 VDC / 3 mA minimum; OFF state at 5 VDC / 1.2 mA maximum), ensuring immune, noise-filtered signal transmission from field contact devices to system memory.

Frequently Asked Questions

Q: What are the exact voltage threshold levels for channel state switching on the 8U-TDILB1?

A: The module registers an ON state at a minimum of 13 VDC (or 3 mA) and an OFF state at a maximum of 5 VDC (or 1.2 mA).

Q: What galvanic isolation rating does the 8U-TDILB1 provide to protect system electronics?

A: The module provides galvanic isolation rated at 1000 VAC RMS or +/-1500 VDC between field input circuits and the system backplane, with an overall insulation specification of 600 V.

Q: What is the maximum current draw of the 8U-TDILB1 module from the power rail?

A: The module has a rated current consumption of 95 mA across its 18 to 30 VDC operating input voltage range.

Field Installation Guidelines

  1. Confirm that cabinet supply power to the field contact loops is within the specified 18 to 30 VDC range before inserting the module.
  2. Align the module edge connector with the designated slot on the Series 8 carrier assembly.
  3. Push the module firmly into place until the backplane connectors fully seat and side retention latches lock onto the rail.
  4. Route field discrete input wiring separately from high-voltage AC lines and power switching cables to avoid induced noise.
  5. Ground all field cable shields at a single ground point on the enclosure cabinet earth bar to maintain galvanic isolation integrity.