{"product_id":"dc-tdil11-digital-input-iota-module-honeywell","title":"DC-TDIL11 Digital Input IOTA Module | Honeywell","description":"\u003cp\u003eThe \u003cstrong\u003eDC-TDIL11\u003c\/strong\u003e (part number 51307782-176) is a 32-channel redundant digital input Input Output Termination Assembly (IOTA) manufactured by Honeywell for Experion PKS C300 controller systems. It conditions and routes 24 VDC discrete signals from field contact switches directly to controller I\/O channels across a redundant backplane connector. Featuring field-selectable internal or external sense power modes, the assembly incorporates integrated fuse barriers and common-mode signal filtering to protect system logic from field-side electrical transients.\u003c\/p\u003e\n\u003ch3\u003eField Sense Power and Channel Protection\u003c\/h3\u003e\n\u003cp\u003eThe 32 discrete digital input points accept a 24 VDC nominal voltage and support non-isolated contact monitoring. Physical jumper links on the IOTA board allow field technicians to select between internal 24 VDC bus supply and external field sense power. Fast-acting integrated fuses protect the shared 24 VDC power distribution loops against short circuits, preventing overcurrent conditions from propagating across adjacent channels during simultaneous contact switching.\u003c\/p\u003e\n\u003ch3\u003eField Installation Guidelines\u003c\/h3\u003e\n\u003cp\u003eWhen installing or servicing the DC-TDIL11 IOTA assembly within an Experion PKS node, observe the following physical installation steps:\u003c\/p\u003e\n\u003col\u003e\n\u003cli\u003eDisconnect main power from field supply terminals before configuring hardware sense power jumpers on the IOTA board.\u003c\/li\u003e\n\u003cli\u003eAlign the module card connectors with the mating IOTA base assembly and press firmly until both locking levers fully engage.\u003c\/li\u003e\n\u003cli\u003eVerify that all 24 VDC field wiring terminations follow correct polarity guidelines.\u003c\/li\u003e\n\u003cli\u003eRoute 24 VDC discrete field input cables separately from high-voltage AC conductors to prevent capacitive coupling and switching noise.\u003c\/li\u003e\n\u003cli\u003eSecure all field wiring shield drain wires to the main system grounding bar using a short, low-impedance connection.\u003c\/li\u003e\n\u003c\/ol\u003e\n\u003cfigure class=\"table\"\u003e\n\u003ctable\u003e\n\u003cthead\u003e\n\u003ctr\u003e\n\u003cth\u003e\u003cstrong\u003eParameter\u003c\/strong\u003e\u003c\/th\u003e\n\u003cth\u003e\u003cstrong\u003eSpecification\u003c\/strong\u003e\u003c\/th\u003e\n\u003c\/tr\u003e\n\u003c\/thead\u003e\n\u003ctbody\u003e\n\u003ctr\u003e\n\u003ctd\u003eModel\u003c\/td\u003e\n\u003ctd\u003eDC-TDIL11\u003c\/td\u003e\n\u003c\/tr\u003e\n\u003ctr\u003e\n\u003ctd\u003ePart Number\u003c\/td\u003e\n\u003ctd\u003e51307782-176 (PWA)\u003c\/td\u003e\n\u003c\/tr\u003e\n\u003ctr\u003e\n\u003ctd\u003eBrand\u003c\/td\u003e\n\u003ctd\u003eHoneywell\u003c\/td\u003e\n\u003c\/tr\u003e\n\u003ctr\u003e\n\u003ctd\u003eProduct Type\u003c\/td\u003e\n\u003ctd\u003eDigital Input Termination Assemblies\u003c\/td\u003e\n\u003c\/tr\u003e\n\u003ctr\u003e\n\u003ctd\u003eSystem Compatibility\u003c\/td\u003e\n\u003ctd\u003eHoneywell Experion PKS C300 Systems\u003c\/td\u003e\n\u003c\/tr\u003e\n\u003ctr\u003e\n\u003ctd\u003eNumber of Inputs\u003c\/td\u003e\n\u003ctd\u003e32 discrete digital input points\u003c\/td\u003e\n\u003c\/tr\u003e\n\u003ctr\u003e\n\u003ctd\u003eInput Voltage\u003c\/td\u003e\n\u003ctd\u003e24 VDC\u003c\/td\u003e\n\u003c\/tr\u003e\n\u003ctr\u003e\n\u003ctd\u003eInput Type\u003c\/td\u003e\n\u003ctd\u003eNon-isolated, field-selectable internal or external sense power\u003c\/td\u003e\n\u003c\/tr\u003e\n\u003ctr\u003e\n\u003ctd\u003ePower Consumption\u003c\/td\u003e\n\u003ctd\u003e6.5 W\u003c\/td\u003e\n\u003c\/tr\u003e\n\u003ctr\u003e\n\u003ctd\u003eProtection\u003c\/td\u003e\n\u003ctd\u003eIntegrated fuse protection on 24 VDC power rails\u003c\/td\u003e\n\u003c\/tr\u003e\n\u003ctr\u003e\n\u003ctd\u003eOperating Temperature\u003c\/td\u003e\n\u003ctd\u003e0 to 60 deg C\u003c\/td\u003e\n\u003c\/tr\u003e\n\u003ctr\u003e\n\u003ctd\u003eModule Dimensions (H × W × D)\u003c\/td\u003e\n\u003ctd\u003e19.1 × 12.7 × 3.8 cm\u003c\/td\u003e\n\u003c\/tr\u003e\n\u003ctr\u003e\n\u003ctd\u003eNet Weight\u003c\/td\u003e\n\u003ctd\u003e0.4 kg\u003c\/td\u003e\n\u003c\/tr\u003e\n\u003ctr\u003e\n\u003ctd\u003eCountry of Origin\u003c\/td\u003e\n\u003ctd\u003eUSA\u003c\/td\u003e\n\u003c\/tr\u003e\n\u003c\/tbody\u003e\n\u003c\/table\u003e\n\u003c\/figure\u003e\n\u003cp\u003eFrequently Asked Questions\u003c\/p\u003e\n\u003cp\u003eQ: Can the Honeywell DC-TDIL11 be replaced without taking down the C300 controller node?\u003c\/p\u003e\n\u003cp\u003eA: Yes, the IOTA architecture supports online replacement when installed in a redundant configuration, provided the companion redundant IOTA channel remains active during the swap.\u003c\/p\u003e\n\u003cp\u003eQ: How is field sense power configured on the DC-TDIL11 digital input IOTA?\u003c\/p\u003e\n\u003cp\u003eA: Selection between internal 24 VDC backplane bus power and external field supply is set via physical hardware jumpers on the IOTA board.\u003c\/p\u003e\n\u003cp\u003eQ: What safeguards prevent short circuits in field wiring from damaging the 24 VDC sense power supply?\u003c\/p\u003e\n\u003cp\u003eA: Integrated fast-acting fuses isolate the shared 24 VDC field distribution loops in the event of an external wiring short circuit.\u003c\/p\u003e","brand":"Honeywell","offers":[{"title":"Default Title","offer_id":68047733948712,"sku":"DC-TDIL11 51307782-176","price":315.0,"currency_code":"USD","in_stock":true}],"thumbnail_url":"\/\/cdn.shopify.com\/s\/files\/1\/0827\/6266\/2184\/files\/DC-TDIL11_Cocoai.png?v=1793347773","url":"https:\/\/www.powerdcs.com\/es\/products\/dc-tdil11-digital-input-iota-module-honeywell","provider":"Power DCS Parts Limited","version":"1.0","type":"link"}