FC-TSDO-04UNI Safety Manager System Module | Honeywell

Specifications

  • Manufacturer: Honeywell

  • Product No.: FC-TSDO-04UNI

  • Condition: 10 Artículos en stock

  • Product Type: Digital Output Modules

  • Product Origin: USA

  • Payment:T/T, Western Union

  • Weight: 3000g

  • Shipping port: Xiamen

  • Warranty: 12 months

Detalles de producto

Descripción

Configured for high-current digital actuation in Safety Manager systems, the Honeywell FC-TSDO-04UNI (FC-TSDO-04UNI Safety Manager System Module) provides direct physical/electrical execution.

Hardware Specifications

Parameter Specification
Model FC-TSDO-04UNI
Brand Honeywell
Weight Shipping Weight: 3 kg
Dimensions 60 x 70 x 54 mm (L x W x H)
Operating Temp -20 to 70 deg C (standard panel ambient)
Power Consumption Power consumption unlisted
Module Type Safety Manager System Module
Number of Channels 4 channels
Maximum Voltage Rating 50 VDC (IEC 1010 Overvoltage Category 3) / 150 VDC (IEC 1010 Overvoltage Category 2)
Max Continuous Current 2 A per channel
Rail Compatibility DIN EN TS32 / TS35 x 7.5 (Used rail length: 61 mm / 2.40 in)
Termination Specifications Screw terminals: Max wire 2.5 mm2 (AWG 14), Strip length 7 mm (0.28 in), Torque 0.5 Nm (0.37 ft-lb)

4-20 mA HART Loop Protocol & Channel-to-Channel Isolation

Designed for high-integrity field device control, the module executes switching operations across 4 high-current output channels rated for up to 2 A continuous load each. Built-in channel-to-channel isolation and physical separation protect internal backplane electronics from field-side voltage transients, maintaining compliance with IEC 1010 overvoltage category standards up to 150 VDC. The isolated output channels prevent common-mode voltage transfer between load circuits, safeguarding overall Safety Manager loop control and system logic execution.

Frequently Asked Questions

Q: What are the strict overvoltage category limits for this output module?

A: The module is rated for a maximum continuous operating voltage of 50 VDC under IEC 1010 Overvoltage Category 3 environments, and up to 150 VDC under IEC 1010 Overvoltage Category 2 field installations.

Q: What are the torque and conductor sizing specifications for field wiring terminals?

A: Screw terminals accept a maximum conductor size of 2.5 mm2 (AWG 14) with a wire strip length of 7 mm (0.28 in). All terminal screws must be tightened strictly to 0.5 Nm (0.37 ft-lb).

Field Installation Guidelines

  • De-energize all field loop power supplies before attaching or removing terminal wiring connections to prevent arc flash hazards.
  • Snap the module base firmly onto standard DIN EN TS32 or TS35 x 7.5 mounting rails, ensuring a minimum dedicated rail length of 61 mm (2.40 in).
  • Strip all field wires precisely to 7 mm (0.28 in) to ensure full contact engagement within the terminal block without leaving exposed bare copper.
  • Torque all terminal screw connections to 0.5 Nm using a calibrated torque screwdriver to maintain gas-tight electrical contact and avoid stripping threads.
  • Route high-current DC output cabling in dedicated grounded conduits segregated from low-voltage sensitive analog signal lines.