Specifications

  • Manufacturer: Honeywell

  • Product No.: FC-TSDO-0824C

  • Condition: 10 Artículos en stock

  • Product Type: Safe Digital Output Modules

  • Product Origin: USA

  • Payment:T/T, Western Union

  • Weight: 80g

  • Shipping port: Xiamen

  • Warranty: 12 months

Detalles de producto

Descripción

Configured for safe discrete output control in Honeywell safety system architectures, the Honeywell FC-TSDO-0824C (FC-TSDO-0824C Safe Digital Output Module) provides direct physical/electrical execution. The module drives 8 discrete output channels, transferring safety-related switching commands from the logic solver backplane directly to field actuators and solenoids.

Hardware Specifications

Parameter Specification
Model FC-TDSO-0824C
Brand Honeywell
Origin USA
Weight 0.08 kg
Dimensions 7 x 6 x 5.8 cm
Operating Temp -20 to +60 deg C
Power Consumption 24 VDC nominal (Load dependent; 1.5 A per channel max)
Module Function Safe digital output signal control
Signal Type Discrete DC output
Number of Channels 8 channels
Maximum Voltage 36 VDC (IEC 1010)
Max Continuous Current 1.5 A per channel
Max Wire Diameter 2.5 mm2 (AWG 14)
Approvals CE, TUV, UL, CSA, FM

Channel Isolation & Field Loop Characteristics

The FC-TSDO-0824C module incorporates channel-to-channel isolation and galvanic isolation barriers between the field wiring and internal backplane logic. The output switching hardware manages DC loads up to 36 VDC while sustaining up to 1.5 A continuous current per channel. Integrated protective filtering suppresses transient inductive spikes caused by de-energizing solenoid coils or field relays, preventing noise reflection back into the central safety logic solver.

Frequently Asked Questions

Q: What is the maximum continuous current capacity per output channel on the FC-TSDO-0824C module?

A: Each individual output channel supports a maximum continuous load current of 1.5 A at operating voltages up to 36 VDC, evaluated under IEC 1010 standards.

Q: What maximum conductor size is supported by the module termination connectors?

A: Terminal blocks on the module accommodate discrete field wiring up to a maximum cross-sectional area of 2.5 mm2 (AWG 14).

Field Installation Guidelines

  • Mechanical Mounting: Seat the module firmly onto the dedicated safety rack baseplate guides inside the control cabinet until the retention latches fully engage.
  • Wiring & Polarity: Terminate discrete load cables at the assigned terminal block. Verify matching DC voltage polarity and ensure conductor sizes do not exceed 2.5 mm2 (AWG 14).
  • Shielding & Grounding: Connect field cable drain wires to the main enclosure earth grounding bar using low-impedance clamps to maintain common-mode noise suppression.
  • Cable Routing: Maintain a minimum separation distance of 30 cm between 24 VDC digital output wiring and high-voltage AC power lines inside panel trunking.