FC-TSGASH-1624P V1.0 Field Termination Assembly | Honeywell
Specifications
Manufacturer: Honeywell
Product No.: FC-TSGASH-1624P
Condition: 10 Artículos en stock
Product Type: Termination Boards
Product Origin: USA
Payment:T/T, Western Union
Weight: 3000g
Shipping port: Xiamen
Warranty: 12 months
Detalles de producto
Descripción
The Honeywell FC-TSGASH-1624P V1.0, also cataloged as the FC-TSGASH-1624P Field Termination Assembly, operates as a dedicated hardware component for 16-channel analog signal routing and power distribution within Honeywell Safety Manager platforms.
Hardware Specifications
| Parameter | Specification |
|---|---|
| Model | FC-TSGASH-1624P V1.0 |
| Brand | Honeywell |
| Origin | USA |
| Weight | 3.0 kg (Shipping) |
| Operating Temp | -10 to +60 deg C |
| Power Consumption | Passive distribution load via 24 VDC supply |
| Input Channels | 16 analog inputs (0-20 mA) |
| Protocol Interface | HART protocol supported on all channels |
| Power Supply Terminal | 24 VDC (2-pole connector) |
| Field Wiring Terminals | Screw terminals for field wiring and chassis ground |
| Mounting Type | DIN EN rail snap-in provision |
4-20 mA HART Loop Protocol & Channel Isolation
The termination assembly conditions and channels 16 independent 0-20 mA analog signals while providing physical line interfaces for HART digital communication pass-through. Built-in channel-to-channel isolation circuits prevent potential ground loop shifts, cross-channel interference, and field line transients from propagating back to the safety processor. High-frequency filtering maintains analog loop integrity without attenuating bi-directional HART carrier signals overlaying the 4-20 mA current loops.
Frequently Asked Questions
Q: Does the FC-TSGASH-1624P V1.0 module require external power connections for field loops?
A: Yes, primary loop power is supplied through the onboard 24 VDC 2-pole connector to power connected 2-wire transmitters across all 16 channels.
Q: How is physical grounding established on the FC-TSGASH-1624P V1.0 terminal assembly?
A: Dedicated screw terminals are provided directly on the board assembly to connect field wire shield drains to the cabinet safety ground rail.
Q: Can HART communicators interface directly across the 0-20 mA channels?
A: Yes, all 16 analog input channels feature frequency-transparent impedance paths designed to support HART digital protocol communication.
Field Installation Guidelines
- Snap the assembly firmly onto the DIN EN mounting rail until the retention clips engage securely.
- Connect the main 24 VDC supply wiring to the 2-pole power connector with correct polarity.
- Wire field loop conductors to the assigned screw terminal blocks according to the loop schematic.
- Separate low-voltage analog cables from high-voltage AC conductors inside control panel wireways.
- Secure all individual shield drain wires directly to the ground screw terminals to ensure full EMI noise rejection.
Cómo obtener una cotización
Rastreo de orden
Transportistas
Política y condiciones de reembolso
Condiciones de garantía
Productos relacionados
- Al elegir una selección, se actualiza la página completa.