{"product_id":"foxboro-fbm216-p0917xq-communication-redundant-input-interface-module","title":"Foxboro FBM216 P0917XQ Communication Redundant Input Interface Module","description":"\u003cp\u003eThe \u003cstrong\u003eFoxboro FBM216 P0917XQ\u003c\/strong\u003e is an 8-channel input interface module supporting HART Protocol v6 over point-to-point, asynchronous, half-duplex links at 1200 baud. It provides group-isolated channels, 15-bit analog resolution with +\/- 0.075% full-scale accuracy, a 100 ms update rate, and cable runs up to 3030 m (10000 ft) per HART FSK specification HCF_SPEC-54 Revision 8.1.\u003c\/p\u003e\n\u003ch3\u003eHART Communication and Timing\u003c\/h3\u003e\n\u003cp\u003eEach of the 8 group-isolated channels communicates point-to-point in a master\/slave, asynchronous, half-duplex arrangement at 1200 baud, reaching up to 2 messages per second. Per-byte parity and a CRC check byte verify message integrity, with a fastest allowed ECB block period of 500 msec.\u003c\/p\u003e\n\u003cp\u003eUnder HART FSK physical layer specification HCF_SPEC-54 Revision 8.1, cable distance between the module and field device reaches up to 3030 m (10000 ft). The interface specifies a minimum compliance voltage of 18 VDC at 20.5 mA.\u003c\/p\u003e\n\u003ch3\u003eAnalog Input Characteristics and Physical Dimensions\u003c\/h3\u003e\n\u003cp\u003eCurrent inputs sense across a 61.9 ohm nominal sense resistor with a 280 ohm minimum total input resistance, 15-bit resolution, and +\/- 0.075% full-scale accuracy including nonlinearity. Signal conditioning features a 100 ms update rate, 500 ms integration time, 50 PPM\/deg C temperature coefficient, greater than 100 dB common mode rejection at 50 or 60 Hz, and greater than 35 dB normal mode rejection at 50 or 60 Hz.\u003c\/p\u003e\n\u003cp\u003eThe module measures 102 mm (4 in) high—or 114 mm (4.5 in) including mounting lugs—by 45 mm (1.75 in) wide by 104 mm (4.11 in) deep, with an approximate mass of 284 g (10 oz). Compatible termination assemblies weigh approximately 181 g (0.40 lb) for compression style and 249 g (0.55 lb) for ring lug style.\u003c\/p\u003e\n\u003ch3\u003eTechnical Specifications\u003c\/h3\u003e\n\u003cfigure class=\"table\"\u003e\n\u003ctable\u003e\n\u003cthead\u003e\n\u003ctr\u003e\n\u003cth\u003e\u003cstrong\u003eParameter\u003c\/strong\u003e\u003c\/th\u003e\n\u003cth\u003e\u003cstrong\u003eSpecification\u003c\/strong\u003e\u003c\/th\u003e\n\u003c\/tr\u003e\n\u003c\/thead\u003e\n\u003ctbody\u003e\n\u003ctr\u003e\n\u003ctd\u003eModel\u003c\/td\u003e\n\u003ctd\u003eFBM216 P0917XQ\u003c\/td\u003e\n\u003c\/tr\u003e\n\u003ctr\u003e\n\u003ctd\u003eBrand\u003c\/td\u003e\n\u003ctd\u003eFoxboro\u003c\/td\u003e\n\u003c\/tr\u003e\n\u003ctr\u003e\n\u003ctd\u003eSupported Protocol\u003c\/td\u003e\n\u003ctd\u003eHART Protocol v6\u003c\/td\u003e\n\u003c\/tr\u003e\n\u003ctr\u003e\n\u003ctd\u003eChannels\u003c\/td\u003e\n\u003ctd\u003e8 group-isolated channels\u003c\/td\u003e\n\u003c\/tr\u003e\n\u003ctr\u003e\n\u003ctd\u003eDevice Communication\u003c\/td\u003e\n\u003ctd\u003ePoint-to-point, master\/slave, asynchronous, half-duplex, 1200 baud\u003c\/td\u003e\n\u003c\/tr\u003e\n\u003ctr\u003e\n\u003ctd\u003eError Checking\u003c\/td\u003e\n\u003ctd\u003eParity on each byte, plus one CRC check byte\u003c\/td\u003e\n\u003c\/tr\u003e\n\u003ctr\u003e\n\u003ctd\u003eMessage Speed\u003c\/td\u003e\n\u003ctd\u003e2 messages per second\u003c\/td\u003e\n\u003c\/tr\u003e\n\u003ctr\u003e\n\u003ctd\u003eFastest ECB Block Period\u003c\/td\u003e\n\u003ctd\u003e500 msec\u003c\/td\u003e\n\u003c\/tr\u003e\n\u003ctr\u003e\n\u003ctd\u003eMaximum Cable Distance\u003c\/td\u003e\n\u003ctd\u003eUp to 3030 m (10000 ft) per HART FSK HCF_SPEC-54 Revision 8.1\u003c\/td\u003e\n\u003c\/tr\u003e\n\u003ctr\u003e\n\u003ctd\u003eCompliance Voltage\u003c\/td\u003e\n\u003ctd\u003e18 VDC minimum at 20.5 mA\u003c\/td\u003e\n\u003c\/tr\u003e\n\u003ctr\u003e\n\u003ctd\u003eSense Resistor\u003c\/td\u003e\n\u003ctd\u003e61.9 ohm nominal\u003c\/td\u003e\n\u003c\/tr\u003e\n\u003ctr\u003e\n\u003ctd\u003eTotal Input Resistance\u003c\/td\u003e\n\u003ctd\u003e280 ohm minimum\u003c\/td\u003e\n\u003c\/tr\u003e\n\u003ctr\u003e\n\u003ctd\u003eAnalog Accuracy\u003c\/td\u003e\n\u003ctd\u003e+\/- 0.075% of full scale (includes nonlinearity)\u003c\/td\u003e\n\u003c\/tr\u003e\n\u003ctr\u003e\n\u003ctd\u003eTemperature Coefficient\u003c\/td\u003e\n\u003ctd\u003e50 PPM\/deg C\u003c\/td\u003e\n\u003c\/tr\u003e\n\u003ctr\u003e\n\u003ctd\u003eResolution\u003c\/td\u003e\n\u003ctd\u003e15 bits\u003c\/td\u003e\n\u003c\/tr\u003e\n\u003ctr\u003e\n\u003ctd\u003eUpdate Rate\u003c\/td\u003e\n\u003ctd\u003e100 ms\u003c\/td\u003e\n\u003c\/tr\u003e\n\u003ctr\u003e\n\u003ctd\u003eIntegration Time\u003c\/td\u003e\n\u003ctd\u003e500 ms\u003c\/td\u003e\n\u003c\/tr\u003e\n\u003ctr\u003e\n\u003ctd\u003eCommon Mode Rejection\u003c\/td\u003e\n\u003ctd\u003eGreater than 100 dB at 50 or 60 Hz\u003c\/td\u003e\n\u003c\/tr\u003e\n\u003ctr\u003e\n\u003ctd\u003eNormal Mode Rejection\u003c\/td\u003e\n\u003ctd\u003eGreater than 35 dB at 50 or 60 Hz\u003c\/td\u003e\n\u003c\/tr\u003e\n\u003ctr\u003e\n\u003ctd\u003eModule Dimensions\u003c\/td\u003e\n\u003ctd\u003e102 mm (4 in) height (114 mm \/ 4.5 in with mounting lugs) x 45 mm (1.75 in) width x 104 mm (4.11 in) depth\u003c\/td\u003e\n\u003c\/tr\u003e\n\u003ctr\u003e\n\u003ctd\u003eModule Mass\u003c\/td\u003e\n\u003ctd\u003e284 g (10 oz) approximate\u003c\/td\u003e\n\u003c\/tr\u003e\n\u003ctr\u003e\n\u003ctd\u003eTermination Assembly Mass\u003c\/td\u003e\n\u003ctd\u003eCompression: 181 g (0.40 lb) approximate; Ring Lug: 249 g (0.55 lb) approximate\u003c\/td\u003e\n\u003c\/tr\u003e\n\u003c\/tbody\u003e\n\u003c\/table\u003e\n\u003c\/figure\u003e\n\u003cp\u003eFrequently Asked Questions\u003c\/p\u003e\n\u003cp\u003eQ: What is the maximum cable distance between the Foxboro FBM216 P0917XQ and a HART field device?\u003c\/p\u003e\n\u003cp\u003eA: It supports distances up to 3030 m (10000 ft) in accordance with HART FSK physical layer specification HCF_SPEC-54 Revision 8.1.\u003c\/p\u003e\n\u003cp\u003eQ: What are the analog accuracy, resolution, and input resistance ratings for current inputs?\u003c\/p\u003e\n\u003cp\u003eA: Current inputs provide 15-bit resolution, +\/- 0.075% full-scale accuracy including nonlinearity, a 61.9 ohm nominal sense resistor, and a 280 ohm minimum total input resistance.\u003c\/p\u003e\n\u003cp\u003eQ: How is serial error checking handled on the HART link?\u003c\/p\u003e\n\u003cp\u003eA: Each byte includes parity checking along with one CRC check byte during 1200 baud point-to-point half-duplex communication.\u003c\/p\u003e","brand":"Foxboro","offers":[{"title":"Default Title","offer_id":68249474892072,"sku":"FBM216 P0917XQ","price":238.0,"currency_code":"USD","in_stock":true}],"thumbnail_url":"\/\/cdn.shopify.com\/s\/files\/1\/0827\/6266\/2184\/files\/FBM216P0922VV.jpg?v=1795139725","url":"https:\/\/www.powerdcs.com\/es\/products\/foxboro-fbm216-p0917xq-communication-redundant-input-interface-module","provider":"Power DCS Parts Limited","version":"1.0","type":"link"}