Honeywell 10213/2/3 Fail-Safe Digital Input Module

Specifications

  • Manufacturer: Honeywell

  • Product No.: 10213/2/3

  • Condition: 10 Artículos en stock

  • Product Type: Digital Input Modules

  • Payment:T/T, Western Union

  • Weight: 250g

  • Shipping port: Xiamen

  • Warranty: 12 months

Detalles de producto

Descripción

The Honeywell 10213/2/3, also cataloged as the 10213/2/3 Digital Input Module, operates as a dedicated hardware component for safety-critical digital signal processing within Safety Manager and FSC platforms.

Hardware Specifications

Parameter Specification
Model 10213/2/3
Brand Honeywell
Origin Netherlands
Channels 4 isolated digital input channels
Field Power Voltage Range 18 to 30 VDC
Input Voltage 5 to 30 VDC
Input Current 3 mA minimum
Input Impedance 4.2 kohm
Input Response Time 5 ms maximum
Isolation Voltage 1000 VAC RMS (system to field)
Operating Temp -40 to 65 deg C
Storage Temp -40 to 65 deg C
Humidity 10 to 90% RH (non-condensing)
Weight 0.25 kg
Dimensions 35.0 mm x 99.5 mm x 114.5 mm (W x H x D)
Power Consumption 2.4 W maximum

Fail-Safe Architecture & Loop Isolation

Designed to meet SIL3 safety instrumented system requirements, the module provides channel-to-backplane galvanic isolation up to 1000 VAC RMS. Continuous onboard self-diagnostics constantly monitor input loop integrity to detect open-circuit and short-circuit field wiring conditions. When a field fault occurs or system power falls below the specified 18 VDC limit, the internal hardware forces affected channels into a predefined fail-safe state, preventing false signal evaluation during safety-critical trips.

Frequently Asked Questions

Q: How does the module handle signal isolation between field devices and the backplane?

A: Integrated optical and galvanic barriers isolate field-side 24 VDC circuits from internal system electronics up to 1000 VAC RMS, suppressing ground loops and voltage transients.

Q: What contact configurations are supported on the field inputs?

A: The module natively interfaces with both Form A (normally open) and Form B (normally closed) dry contacts powered by a field supply between 18 and 30 VDC.

Q: What triggers an automatic diagnostic fault condition on an input loop?

A: Onboard diagnostic routines constantly monitor loop impedance and current. Any detected open circuit or shorted input condition automatically trip a channel diagnostic flag without disrupting power to adjacent channels.

Field Installation Guidelines

  1. Mount the module securely into its designated rack slot before applying field power to the terminal block.
  2. Verify field supply voltage remains within the rated 18 to 30 VDC tolerance prior to turning on field loop power.
  3. Terminate shielded signal cables according to system grounding standards, maintaining a single-point earth ground to eliminate noise coupling.
  4. Maintain a minimum bending radius for signal wiring inside cable ducts to prevent terminal strain and conductor fatigue.
  5. Ensure ambient operating temperature within the cabinet stays within the specified -40 to 65 deg C range using appropriate cabinet ventilation.

Cómo obtener una cotización

Rastreo de orden

Transportistas

Política y condiciones de reembolso

Condiciones de garantía