{"product_id":"honeywell-cc-taid01-51306733-175-experion-pks-analog-input-iota","title":"Honeywell CC-TAID01 51306733-175 Experion PKS Analog Input IOTA","description":"\u003cp\u003eThe \u003cstrong\u003eHoneywell CC-TAID01 51306733-175\u003c\/strong\u003e is a 16-channel differential analog input Input Output Termination Assembly (IOTA) engineered for the Experion PKS C-Series distributed control system. Operating on a 24 VDC power supply, it conditions field analog signals from transmitters and sensors, converting process inputs into high-resolution digital data for central controller execution.\u003c\/p\u003e\n\u003ch3\u003eSignal Processing and System Isolation\u003c\/h3\u003e\n\u003cp\u003eThe assembly accommodates multiple high-level analog signal standards across its 16 differential channels, including 0-10 V, 0-5 V, 1-5 V, and 4-20 mA inputs. Featuring 16-bit analog-to-digital conversion resolution and a full-scale accuracy of +\/- 0.1%, it incorporates 500 Vrms channel isolation to protect system electronics against field transients and noise.\u003c\/p\u003e\n\u003ch3\u003eMounting and Environmental Operating Limits\u003c\/h3\u003e\n\u003cp\u003eDesigned for standard DIN rail mounting within Experion C-Series cabinets, the CC-TAID01 supports user-configurable sampling rates to match loop response requirements. The assembly operates across an extended ambient temperature range of -40 deg C to +70 deg C and relative humidity conditions between 5% and 95% RH (non-condensing).\u003c\/p\u003e\n\u003cfigure class=\"table\"\u003e\n\u003ctable\u003e\n\u003cthead\u003e\n\u003ctr\u003e\n\u003cth\u003e\u003cstrong\u003eParameter\u003c\/strong\u003e\u003c\/th\u003e\n\u003cth\u003e\u003cstrong\u003eSpecification\u003c\/strong\u003e\u003c\/th\u003e\n\u003c\/tr\u003e\n\u003c\/thead\u003e\n\u003ctbody\u003e\n\u003ctr\u003e\n\u003ctd\u003eModel\u003c\/td\u003e\n\u003ctd\u003eCC-TAID01 (Part Number 51306733-175)\u003c\/td\u003e\n\u003c\/tr\u003e\n\u003ctr\u003e\n\u003ctd\u003eBrand\u003c\/td\u003e\n\u003ctd\u003eHoneywell\u003c\/td\u003e\n\u003c\/tr\u003e\n\u003ctr\u003e\n\u003ctd\u003eProduct Type\u003c\/td\u003e\n\u003ctd\u003eAnalog Input IOTA\u003c\/td\u003e\n\u003c\/tr\u003e\n\u003ctr\u003e\n\u003ctd\u003eSystem Series\u003c\/td\u003e\n\u003ctd\u003eExperion PKS C-Series\u003c\/td\u003e\n\u003c\/tr\u003e\n\u003ctr\u003e\n\u003ctd\u003eNumber of Channels\u003c\/td\u003e\n\u003ctd\u003e16 differential channels\u003c\/td\u003e\n\u003c\/tr\u003e\n\u003ctr\u003e\n\u003ctd\u003eInput Signal Types\u003c\/td\u003e\n\u003ctd\u003e0-10 V, 0-5 V, 1-5 V, 4-20 mA\u003c\/td\u003e\n\u003c\/tr\u003e\n\u003ctr\u003e\n\u003ctd\u003eInput Impedance\u003c\/td\u003e\n\u003ctd\u003eHigh impedance\u003c\/td\u003e\n\u003c\/tr\u003e\n\u003ctr\u003e\n\u003ctd\u003eResolution\u003c\/td\u003e\n\u003ctd\u003e16-bit\u003c\/td\u003e\n\u003c\/tr\u003e\n\u003ctr\u003e\n\u003ctd\u003eAccuracy\u003c\/td\u003e\n\u003ctd\u003e+\/- 0.1% of full scale\u003c\/td\u003e\n\u003c\/tr\u003e\n\u003ctr\u003e\n\u003ctd\u003eIsolation Voltage\u003c\/td\u003e\n\u003ctd\u003e500 Vrms\u003c\/td\u003e\n\u003c\/tr\u003e\n\u003ctr\u003e\n\u003ctd\u003ePower Supply Voltage\u003c\/td\u003e\n\u003ctd\u003e24 VDC\u003c\/td\u003e\n\u003c\/tr\u003e\n\u003ctr\u003e\n\u003ctd\u003eMounting Type\u003c\/td\u003e\n\u003ctd\u003eDIN rail\u003c\/td\u003e\n\u003c\/tr\u003e\n\u003ctr\u003e\n\u003ctd\u003eOperating Temperature Range\u003c\/td\u003e\n\u003ctd\u003e-40 deg C to +70 deg C\u003c\/td\u003e\n\u003c\/tr\u003e\n\u003ctr\u003e\n\u003ctd\u003eOperating Humidity Range\u003c\/td\u003e\n\u003ctd\u003e5% to 95% RH (non-condensing)\u003c\/td\u003e\n\u003c\/tr\u003e\n\u003c\/tbody\u003e\n\u003c\/table\u003e\n\u003c\/figure\u003e\n\u003ch3\u003eFrequently Asked Questions\u003c\/h3\u003e\n\u003cp\u003eQ: What field analog input signals are supported by the Honeywell CC-TAID01 51306733-175 IOTA? A: It supports voltage input ranges of 0-10 V, 0-5 V, and 1-5 V, as well as 4-20 mA current loop signals across 16 differential channels.\u003c\/p\u003e\n\u003cp\u003eQ: What isolation level is provided on the CC-TAID01 terminal assembly? A: The module features 500 Vrms isolation to protect backplane processing logic from field-side electrical interference.\u003c\/p\u003e","brand":"Honeywell","offers":[{"title":"Default Title","offer_id":67949575405864,"sku":"CC-TAID01 51306733-175","price":315.0,"currency_code":"USD","in_stock":true}],"thumbnail_url":"\/\/cdn.shopify.com\/s\/files\/1\/0827\/6266\/2184\/files\/51306733-175_Cocoai.png?v=1792571097","url":"https:\/\/www.powerdcs.com\/es\/products\/honeywell-cc-taid01-51306733-175-experion-pks-analog-input-iota","provider":"Power DCS Parts Limited","version":"1.0","type":"link"}