Honeywell Experion PKS Series-C Fieldbus Baseplate | CC-TFE021
Specifications
Manufacturer: Honeywell
Product No.: CC-TFE021
Condition: 10 Artículos en stock
Product Type: I/O Baseplates
Product Origin: USA
Payment:T/T, Western Union
Weight: 800g
Shipping port: Xiamen
Warranty: 12 months
Detalles de producto
Descripción
The Honeywell CC-TFE021, also cataloged as the CC-TFE021 FOUNDATION Fieldbus Interface Module (FIM) Baseplate, operates as a dedicated hardware component for backplane power distribution and network routing within Honeywell Experion PKS Series-C platforms.
Hardware Specifications
| Parameter | Specification |
|---|---|
| Model | CC-TFE021 |
| Brand | Honeywell |
| Origin | USA |
| Weight | 0.8 kg |
| Dimensions | 304.8 mm x 127.0 mm x 50.8 mm |
| Operating Temp | -40 to +70 deg C |
| Power Consumption | Redundant 24 VDC bus input execution |
| Part Number | 51306713-175 |
| Module Slots | 2 slots for FIM4 / FIM8 modules |
| Network Topology | FOUNDATION Fieldbus H1 interface support |
| Conformal Coating | G3 level harsh environment protection |
| Storage Temp | -40 to +85 deg C |
| Relative Humidity | 5% to 95% (non-condensing) |
| Mounting | Panel mount or standard cabinet mounting |
FOUNDATION Fieldbus / Profibus PA Connectivity and Power Routing
The Honeywell CC-TFE021 provides hardware backplane connections designed for FOUNDATION Fieldbus H1 and Profibus PA communications across Experion PKS Series-C controller networks. The baseplate routes redundant 24 VDC power rails directly to mounted Fieldbus Interface Modules while enforcing electrical isolation between high-speed system control buses and field segment connections. Integrated signal paths suppress transient coupling, preserving message timing and deterministic packet transmission across fieldbus segments.
Frequently Asked Questions
Q: How many Fieldbus Interface Modules can be mounted on the CC-TFE021 baseplate?
A: The CC-TFE021 baseplate features dual module slots, allowing up to two Series-C FIM modules to be installed simultaneously in either standalone or redundant operational modes.
Q: Does replacing a FIM module on the CC-TFE021 disrupt communications on adjacent slots?
A: No, the baseplate supports online hot-swapping of individual FIM modules, permitting insertion or removal without removing system power or interrupting active control loops on the secondary slot.
Q: Is external power wiring connected directly to the baseplate board?
A: Yes, redundant 24 VDC system power supplies and fault indication contacts wire directly to the terminal blocks integrated onto the baseplate assembly.
Field Installation Guidelines
- Secure the baseplate to the cabinet backpanel using specified mounting screws, ensuring solid metal-to-metal contact at grounding points to establish chassis ground continuity.
- Route primary and redundant 24 VDC power feeds to the dedicated power terminal blocks, verifying correct voltage levels and wiring polarity prior to energizing.
- Connect Ethernet system cables and H1 fieldbus segment lines to their respective baseplate ports, securing shield ground connections to the cabinet single-point ground bus.
- Align the guide pins of the FIM module with the target slot on the CC-TFE021 baseplate and press firmly until the locking lever fully latches into position.
- Maintain a minimum vertical clearance of 100 mm above and below the baseplate assembly within the panel enclosure to ensure proper convective cooling airflow.