Honeywell FC-MCAR-01 Module Carrier
Specifications
Manufacturer: Honeywell
Product No.: FC-MCAR-01
Condition: 10 Artículos en stock
Product Type: Mounting Plates
Product Origin: USA
Payment:T/T, Western Union
Weight: 3000g
Shipping port: Xiamen
Warranty: 12 months
Detalles de producto
Descripción
Configured for high-density I/O cluster mounting and heavy-duty power distribution in Safety Manager and Fail Safe Control platforms, the Honeywell FC-MCAR-01, also cataloged as the FC-MCAR-01 Module Carrier Panel, provides direct physical/electrical execution.
Hardware Specifications
| Parameter | Specification |
|---|---|
| Model | FC-MCAR-01 |
| Brand | Honeywell |
| Origin | USA |
| Operating Temp | -42 to +70 deg C |
| Power Consumption | Passive distribution load (40 A max supply rail) |
| Nominal Voltage | 24 VDC (-45% to +32%) |
| Internal Logic Current | 4 A maximum |
| Safety Certification | SIL 3 (IEC 61508), TUV |
| Mounting Style | Panel or rack mounting |
Cold Junction Compensation & Channel Isolation
The module carrier backplane provides dedicated high-current supply busbars and signal routing paths for installed analog and digital modules. High-density channel-to-channel isolation across backplane connectors mitigates ground loop current shifts and field line noise transients. This isolated physical infrastructure preserves low-level signal integrity and cold junction compensation reference values across connected 4-20 mA HART loop protocol analog input channels, preventing measurement drift in high-density safety architectures.
Frequently Asked Questions
Q: What is the maximum current capacity supported on the primary supply rail of the FC-MCAR-01?
A: The backplane supply rail supports a maximum current capacity of 40 A at 24 VDC nominal voltage.
Q: Can different types of I/O modules be populated on a single FC-MCAR-01 carrier?
A: Yes, the board serves as a universal carrier supporting mixed configurations of Honeywell Safety Manager analog and digital I/O modules.
Q: What mounting orientation is recommended to optimize thermal performance up to +70 deg C?
A: Vertical cabinet mounting is recommended to facilitate natural convection airflow across installed modules and carrier power busbars.
Field Installation Guidelines
- Mount the carrier plate securely onto the panel frame or 19-inch rack enclosure using specified mounting hardware.
- Verify that cabinet earth grounding straps connect directly to the main grounding stud on the carrier chassis.
- Connect main 24 VDC power feed conductors to the primary power input terminals, ensuring correct polarity.
- Insert I/O modules firmly into their respective slot guide rails until backplane connectors fully seat and latching mechanisms engage.
- Keep high-voltage AC wiring isolated from low-voltage DC power and field signal lines within panel wireways.
Cómo obtener una cotización