Honeywell FC-TSDI-16UNI Safety Manager System Module
Specifications
Manufacturer: Honeywell
Product No.: FC-TSDL-16UNI
Condition: 10 Artículos en stock
Product Type: Digital Input Modules
Product Origin: USA
Payment:T/T, Western Union
Weight: 2000g
Shipping port: Xiamen
Warranty: 12 months
Detalles de producto
Descripción
The Honeywell FC-TSDI-16UNI, also cataloged as the FC-TSDI-16UNI Safety Manager System Module, operates as a dedicated hardware component for safe 16-channel discrete input processing within Honeywell Safety Manager platforms.
Hardware Specifications
| Parameter | Specification |
|---|---|
| Model | FC-TSDI-16UNI |
| Brand | Honeywell |
| Origin | USA |
| Weight | Shipping Weight: 2 kg |
| Dimensions | 90 x 70 x 60 mm (L x W x H) |
| Operating Temp | -20 to 70 deg C (standard panel ambient) |
| Power Consumption | Power consumption dependent on backplane and loop excitation draw |
| Module Type | Safety Manager System Module |
| Channels | 16 channels (2 groups of 8) |
| Maximum Voltage Rating | 50 VDC (IEC 61010-1 Overvoltage Category 3), 150 VDC (IEC 61010-1 Overvoltage Category 2) |
| Rail Mounting | DIN EN rails TS32 / TS35 x 7.5 (Used length: 91 mm / 3.58 in) |
| Fuse Specification | 250 mAT slow-acting (5 x 20 mm / 0.2 x 0.79 in) |
| Field Terminals | Screw terminals, max wire size 2.5 mm2 (AWG 14), strip length 7 mm, tightening torque 0.5 Nm (0.37 ft-lb) |
| Certifications | CE, TUV, UL, CSA, FM |
4-20 mA HART Loop Protocol & Channel-to-Channel Isolation
Designed for critical discrete input monitoring in safety-instrumented setups, the module provides isolated field contact interfacing across two distinct groups of 8 channels. Internal channel-to-channel isolation de-couples field-side potential differences, preventing ground loops and stray high-voltage transients from degrading signal accuracy or interfering with adjacent analog 4-20 mA HART instrument wiring runs within the same control enclosure.
Frequently Asked Questions
Q: What are the electrical wiring limits for field connections on the FC-TSDI-16UNI screw terminal block?
A: The integral screw terminals accept a maximum wire cross-section of 2.5 mm2 (AWG 14) with a strip length of 7 mm (0.28 in) and must be torqued to 0.5 Nm (0.37 ft-lb).
Q: How is individual channel group protection handled on this module?
A: Circuit protection is enforced using an internal 250 mAT slow-acting fuse measuring 5 x 20 mm, designed to interrupt overcurrent conditions on field lines before affecting central backplane logic.
Field Installation Guidelines
- Isolate all field power sources and rack backplane power before attaching or removing module wiring harnesses.
- Mount the assembly securely onto standard TS32 or TS35 x 7.5 DIN rails, ensuring a minimum rail length engagement of 91 mm.
- Strip field conductors to exactly 7 mm and tighten screw terminals to 0.5 Nm to prevent loose contacts or thermal stress.
- Maintain separate raceways for discrete input field cables to avoid electromagnetic cross-talk from high-voltage AC cables.
- Connect all field cable shield drain wires to a central ground bus at a single point to maintain isolation integrity.
Cómo obtener una cotización
Rastreo de orden
Transportistas
Política y condiciones de reembolso
Condiciones de garantía
Productos relacionados