Honeywell MC-GAOX02 51304638-175 Analog Output FTA
Specifications
Manufacturer: Honeywell
Product No.: MC-GAOX02 51304638-175
Condition: 10 Artículos en stock
Product Type: Analog Output Modules
Product Origin: USA
Payment:T/T, Western Union
Weight: 300g
Shipping port: Xiamen
Warranty: 12 months
Detalles de producto
Descripción
The Honeywell 51304638-175, also cataloged as the MC-GAOX02 Analog Output FTA, operates as a dedicated hardware component for multi-channel current signal conditioning and loop driving within Honeywell TDC 3000 and Experion PKS DCS platforms.
Hardware Specifications
| Parameter | Specification |
|---|---|
| Model | MC-GAOX02 51304638-175 |
| Brand | Honeywell |
| Origin | USA |
| Dimensions | 307 mm (12.1 in) length (Size B form factor) |
| Operating Temp | 0 to 60 deg C |
| Power Consumption | Powered via 24 VDC I/O bus interface |
| Output Channels | 8 channels |
| Signal Range | Galvanically isolated 4-20 mA |
| Load Resistance | Less than 750 ohm |
| Termination Type | Compression-type terminals |
| Compliance & Protection | CE compliant, conformal coated |
| Redundancy | Not supported |
Process Control Integration & Channel Isolation
The MC-GAOX02 drives 8 galvanically isolated 4-20 mA current loops connected to control valves, positioners, and field actuators. Integrating directly with 4-20 mA HART loop protocol environments and DCS I/O processors, the board incorporates individual galvanic isolation layers across output channels. This decouples field wiring loops from internal backplane electronics, preventing common-mode voltage surges and ground loops from compromising loop performance across maximum field load resistances up to 750 ohm.
Frequently Asked Questions
Q: What is the maximum allowable load resistance for field devices connected to the MC-GAOX02?
A: Connected field loops and actuator inputs must maintain a total load resistance of less than 750 ohm per channel.
Q: How are field wiring connections terminated on the MC-GAOX02 board assembly?
A: Field conductors connect directly to onboard compression-type terminal blocks mounted along the edge of the Size B board.
Q: Does the MC-GAOX02 support redundant I/O processor topologies?
A: No, the MC-GAOX02 is a non-redundant Field Termination Assembly designed for single-path I/O channel allocation.
Field Installation Guidelines
- Isolate loop power supplies and disconnect system I/O cables before installing or removing the MC-GAOX02 assembly from the carrier rack.
- Strip 4-20 mA field loop conductors to specified lengths and secure them firmly into the compression terminal blocks using appropriate screwdrivers.
- Route field wiring using twisted-pair shielded cables to maintain signal integrity and mitigate high-frequency noise interference.
- Connect all cable shields to a single central panel ground terminal bar, avoiding dual-ended shield grounding to prevent circulating loop currents.
Cómo obtener una cotización
Rastreo de orden
Transportistas
Política y condiciones de reembolso
Condiciones de garantía
Productos relacionados
- Al elegir una selección, se actualiza la página completa.