Honeywell R4343E1014 Relay Flame Detector
Specifications
Manufacturer: Honeywell
Product No.: R4343E1014
Condition: 10 Artículos en stock
Product Type: Flame Detectors
Product Origin: USA
Payment:T/T, Western Union
Weight: 2000g
Shipping port: Xiamen
Warranty: 12 months
Detalles de producto
Descripción
The Honeywell R4343E1014 is an industrial relay flame detector belonging to the R4343D/E series. Engineered for intermittent operation in commercial and industrial burner installations, it reliably indicates the presence or absence of a flame by interfacing with compatible UV flame sensors to maintain burner management safety.
Sensor Compatibility and Output Configuration
This specific R4343E model is designed for use with Honeywell UV sensor models C7027, C7035, and C7044. It features a fast flame failure response time of under 1 second and provides a 1xDPDT output configuration powered by a supply voltage of 220 to 240 Vac.
Environmental and Compliance Ratings
Built in Germany, the unit carries CE approval according to EN298 for intermittent operation and is rated to an IP40 protection class. It operates within an ambient temperature range of -10 deg C to 60 deg C and handles a maximum relative humidity of 90% non-condensing.
| Parameter | Specification |
|---|---|
| Model | R4343E1014 |
| Brand | Honeywell |
| Country of Manufacture | Germany |
| Product Type | Relay Flame Detector |
| Series | R4343D/E series |
| Operation Type | Intermittent operation |
| Compatible Sensors | Honeywell UV sensors C7027, C7035, and C7044 |
| Flame Failure Response Time | < 1 s |
| Outputs | 1xDPDT |
| Supply Voltage | 220 to 240 Vac |
| Protection Class | IP40 |
| Ambient Temperature | -10 deg C to 60 deg C |
| Maximum Humidity | 90% RH, non-condensing |
| Shipping Weight | 2 kg |
Frequently Asked Questions
Q: What type of flame sensors are compatible with the Honeywell R4343E1014?
A: It is designed for use with Honeywell UV sensor models C7027, C7035, and C7044.
Q: What is the flame failure response time of this detector?
A: The flame failure response time is less than 1 second.
Q: What power supply voltage does the unit require? A: It requires a supply voltage of 220 to 240 Vac.