Honeywell R7140L1009/U Burner Control Module
Specifications
Manufacturer: Honeywell
Product No.: R7140L1009/U
Condition: 10 Artículos en stock
Product Type: Burner Control Modules
Product Origin: USA
Payment:T/T, Western Union
Weight: 5000g
Shipping port: Xiamen
Warranty: 12 months
Detalles de producto
Descripción
The R7140L1009/U is a microprocessor-based integrated burner control module manufactured by Honeywell to serve as an upgrade replacement programming control for legacy BC7000 or R4140 systems. Operating on a 120 VAC supply voltage at 50 or 60 Hz, this unit provides automatic burner sequencing, flame supervision, system status indication, and self-diagnostics for gas, oil, or combination fuel single burner applications.
System Configuration and Required Components
To complete installation, the control module requires a compatible ST7800 plug-in purge timer card and an appropriate R78 series flame signal amplifier, such as R7847, R7848, R7849, R7851, R7852, R7861, or R7886 variants. It features configurable pre-purge timing determined by the ST7800A purge timer card, early spark termination at 5 seconds, a 15-second post-purge cycle, and proven low and high fire interlocks.
| Parameter | Specification |
|---|---|
| Model Number | R7140L1009/U |
| Brand | Honeywell |
| Application | Upgrade Replacement Programming Control for R4140 or BC7000 |
| Supply Voltage | 120 VAC (+10, -15%) |
| Frequency | 50 Hz / 60 Hz (+/- 10%) |
| Post-Purge | 15 sec |
| Early Spark Termination | Yes, 5 sec |
| Interlocks | Lockout |
| Dimensions | 177 x 156 x 146 mm (7 x 6 5/32 x 5 3/4 in.) |
| Weight | 1.4 kg (3 lb 1 oz) |
| Shipping and Storage Temperature | -40 deg C to +60 deg C (-40 F to +140 F) |
| Approvals | UL Component Recognized (File MP268), FCC Part 15 Class B |
Frequently Asked Questions
Q: What legacy programming controls is the R7140L1009/U designed to replace?
A: It serves as an upgrade replacement control for Honeywell BC7000 or R4140 legacy programmer controls.
Q: What additional components are required to operate this burner control module?
A: It requires an ST7800 plug-in purge timer card and a compatible R78 series flame signal amplifier to complete the replacement setup.