MC-HPFX02 51304362-175 Honeywell 15-Slot Card File Assembly
Specifications
Manufacturer: Honeywell
Product No.: MC-HPFX02
Condition: 10 Artículos en stock
Product Type: Card Chassis Assemblies
Product Origin: USA
Payment:T/T, Western Union
Weight: 560g
Shipping port: Xiamen
Warranty: 12 months
Detalles de producto
Descripción
Configured for multi-module backplane bus power distribution and I/O card housing in Experion PKS and TPS DCS platforms, the Honeywell 51304362-175 (MC-HPFX02 15-Slot Card File Assembly) provides direct physical/electrical execution.
Hardware Specifications
| Parameter | Specification |
|---|---|
| Model | MC-HPFX02 51304362-175 |
| Brand | Honeywell |
| Origin | USA |
| Weight | 0.56 kg |
| Dimensions | 31.3 x 27.8 x 3 cm |
| Operating Temp | 0 to 60 deg C |
| Power Consumption | Passive backplane assembly (powered via system 24 VDC bus) |
| Slot Capacity | 15 I/O and controller module slots |
| Compatible Modules | Honeywell analog, digital, and specialty I/O cards |
| Configuration | Supports redundant power supply routing and dual-I/O links |
Process Control & Channel Isolation
The MC-HPFX02 card file assembly establishes backplane power distribution and signal routing across 15 hardware slots, connecting analog, digital, and specialty I/O modules to system controllers. Supporting 4-20 mA HART loop protocol architectures, the backplane structure maintains physical channel-to-channel isolation between adjacent module slots, suppressing common-mode bus noise and ground potential shifts across redundant controller and power supply configurations.
Frequently Asked Questions
Q: How does the MC-HPFX02 backplane accommodate redundant power supplies?
A: The internal bus structure incorporates dual power input paths that accept independent 24 VDC feeds, maintaining card file operation if one power module drops offline.
Q: What module types can be installed into the 15 available slots on the MC-HPFX02 assembly?
A: The card file houses Honeywell analog input/output, digital I/O, pulse input, and dedicated serial communication cards compatible with TPS and Experion PKS platforms.
Q: Can modules be inserted into the card file while the assembly is energized?
A: Module replacement must adhere to Honeywell live-insertion guidelines for the specific controller platform to prevent transient power surges on the internal bus lines.
Field Installation Guidelines
- Mount the MC-HPFX02 card file assembly securely onto the cabinet frame using panel screws, torquing fasteners to 1.5 Nm to maintain frame grounding.
- Route primary and redundant 24 VDC power bus cables to the backplane input terminals, verifying correct polarity before applying power.
- Connect the main frame earthing strap directly to the cabinet ground bar using heavy-gauge copper grounding wire to minimize EMI interference.
- Verify that module guide rails are free of debris and insert I/O cards firmly until retaining latches click into place.