MC-TAIH13 51309138-175 Honeywell Analog Input Board
Specifications
Manufacturer: Honeywell
Product No.: MC-TAIH13 51309138-175
Condition: 10 Artículos en stock
Product Type: Analog Input Modules
Product Origin: USA
Payment:T/T, Western Union
Weight: 600g
Shipping port: Xiamen
Warranty: 12 months
Detalles de producto
Descripción
The Honeywell 51309138-175, also cataloged as the MC-TAIH13 High-Level Analog Input Module, operates as a dedicated hardware component for multi-channel analog signal acquisition within Honeywell TotalPlant Solution (TPS) DCS platforms.
Hardware Specifications
| Parameter | Specification |
|---|---|
| Model | MC-TAIH13 51309138-175 |
| Brand | Honeywell |
| Origin | USA |
| Weight | 0.56 kg |
| Dimensions | 31.3 cm x 27.8 cm x 3 cm |
| Operating Temp | -20 to 60 deg C |
| Power Consumption | Powered via 24 VDC I/O bus interface |
| Input Channels | 32 high-level analog input channels |
| Input Voltage Range | -10 V to +30 V |
| Resolution | High-resolution ADC signal digitization |
Fieldbus Protocol & Channel Isolation
The MC-TAIH13 conditions and digitizes up to 32 high-level analog inputs across a wide -10 V to +30 V signal range, interfacing directly with temperature, pressure, and flow transmitter loops. Fully integrated with 4-20 mA HART loop protocol architectures and DCS I/O bus networks, the assembly provides hardware filtering and channel-to-channel isolation to block common-mode noise, preventing signal interference from distorting process variable registers.
Frequently Asked Questions
Q: How many analog sensor loops can be wired directly to the MC-TAIH13 assembly?
A: The board features termination points for up to 32 high-level analog input channels.
Q: What input signal voltage range is accepted across the channel terminals?
A: The hardware supports a wide voltage signal range spanning -10 V to +30 V.
Q: Is external logic power required to operate the MC-TAIH13 assembly?
A: Logic power is provided directly through the standard 24 VDC I/O bus interface connected to the assembly.
Field Installation Guidelines
- Disconnect all 24 VDC power buses and field loop wiring before mounting or replacing the MC-TAIH13 board in the cabinet rack.
- Route all incoming field sensor lines using shielded twisted-pair cables to safeguard low-level analog signals against electromagnetic interference.
- Ground cable shields at a single central cabinet earthing point to prevent circulating ground currents across non-isolated references.
- Align the board with the enclosure mounting rails and secure all retaining screws to ensure proper physical frame grounding.