MU-TDOR12 Honeywell Digital Relay Output Board

Specifications

  • Manufacturer: Honeywell

  • Product No.: MU-TDOR12 51309148-125

  • Condition: 10 Artículos en stock

  • Product Type: Digital Output Cards

  • Product Origin: USA

  • Payment:T/T, Western Union

  • Weight: 720g

  • Shipping port: Xiamen

  • Warranty: 12 months

Detalles de producto

Descripción

The Honeywell MU-TDOR12, also cataloged as the 51309148-125 Digital Relay Output Board, operates as a dedicated hardware component for 32-channel relay-based discrete signal switching within Honeywell Series 8 and Experion PKS platforms.

Hardware Specifications

Parameter Specification
Model MU-TDOR12 (Part Number: 51309148-125)
Brand Honeywell
Origin USA
Weight 0.45 kg
Operating Temp 0 to +50 deg C
Power Consumption Passive field relay coil bus load
Output Density 32 relay output channels
Rated Voltage 24 VDC nominal (19.2-30 VDC range)
Isolation Voltage 1500 V RMS field-to-logic, 500 V RMS group-to-group
Switching Response Time <=0.1 ms ON/OFF typical

4-20 mA HART Loop Protocol & Channel Isolation

The digital relay output board provides galvanic separation across output groups to isolate discrete field actuators from control logic backplanes. With 1500 V RMS field-to-logic dielectric withstand capability, high-voltage inductive spikes from solenoid coils or contactors are contained directly at the terminal stage. This suppression prevents transient noise propagation and ground potential shifts from interfering with high-accuracy analog signals operating on 4-20 mA HART loop protocol connections in adjacent system slots.

Frequently Asked Questions

Q: Does the MU-TDOR12 support hot-swapping under powered rack conditions?

A: Yes, the board features a hot-swappable architecture that allows insertion and removal without interrupting main system power or backplane communication to adjacent modules.

Q: What are the primary isolation boundaries across the output terminals?

A: The board provides 1500 V RMS galvanic isolation between field terminal connections and internal logic circuitry, along with 500 V RMS isolation between output channel groups.

Q: What is the typical response delay for channel state execution?

A: The output channel switching response time is <=0.1 ms typical for both ON and OFF transition states.

Field Installation Guidelines

  1. Ensure the module locking levers are fully disengaged before inserting the board into the designated rack slot.
  2. Push the card horizontally into the guide rails until the rear backplane connectors make contact, then seat the latches securely.
  3. Tighten the module retaining screws to secure chassis grounding and prevent mechanical loosening under operational vibration.
  4. Verify external field power remains within the 19.2 to 30 VDC range before energizing connected relay load circuits.
  5. Dress output field wiring with strain relief mechanisms, separating 24 VDC discrete lines from sensitive analog input wiring.

Cómo obtener una cotización

Rastreo de orden

Transportistas

Política y condiciones de reembolso

Condiciones de garantía

Productos relacionados