Triconex 3401 Digital Output Module
Specifications
Manufacturer: Triconex
Product No.: 3401
Condition: 10 Artículos en stock
Product Type: Digital Output Modules
Product Origin: USA
Payment:T/T, Western Union
Weight: 300g
Shipping port: Xiamen
Warranty: 12 months
Detalles de producto
Descripción
The Triconex 3401 is a 16-channel digital output module engineered for safety-critical industrial applications. It features robust common-ground output switching with integrated diagnostic coverage, operating across a nominal 24 VDC range to ensure reliable control and fault detection in demanding environments.
Output Performance and Voltage Characteristics
The module delivers reliable digital signal switching across its 16 channels, supporting a typical switching current of 3.0 A with a self-limiting maximum below 4.8 A. It operates on a nominal 24 VDC supply within an operational voltage range of 15 VDC to 30 VDC, and accommodates an absolute maximum output voltage of 33 VDC.
Advanced Diagnostics and Loop-Back Monitoring
Built-in diagnostic functions monitor for open circuits, short circuits, power faults, and output states via continuous loop-back scanning. The loop-back mechanism completes a full scan of all 16 points in under 1.0 ms, utilizing specific voltage thresholds to distinguish between off regions, transition regions, and on states.
Environmental Adaptability
Designed to withstand unconditioned industrial settings, the unit functions reliably across a broad ambient temperature range of -40 deg C to 70 deg C. It also accommodates relative humidity levels from 5% to 95% under non-condensing conditions, supporting stable long-term operation in critical control loops.
| Parameter | Specification |
|---|---|
| Model | 3401 |
| Brand | Triconex |
| Product Type | Digital Output Module |
| Output Channels | 16, common ground |
| Nominal Output Voltage | 24 VDC |
| Operational Voltage Range | 15 VDC to 30 VDC |
| Absolute Max Output Voltage | 33 VDC |
| Switching Current | < 4.8 A (self-limiting); 3.0 A typical |
| On-State Voltage Drop | < 1.0 V DC @ 1.5 A |
| Leakage Current (Off State) | < 1 mA |
| Loop-Back Scan Time | < 1.0 ms for all 16 points |
| Operating Temperature | -40 deg C to 70 deg C |
| Relative Humidity | 5% to 95%, non-condensing |
Frequently Asked Questions
Q: What is the nominal operating voltage and current rating for the Triconex 3401 module?
A: The module operates at a nominal 24 VDC (within an operational range of 15 VDC to 30 VDC) and supports a typical switching current of 3.0 A per channel, with a self-limiting maximum below 4.8 A.
Q: How does the module handle diagnostic monitoring and loop-back scans?
A: It provides continuous diagnostic coverage for open circuits, short circuits, and power faults, executing a full loop-back scan across all 16 points in under 1.0 ms.
Cómo obtener una cotización
Rastreo de orden
Transportistas
Política y condiciones de reembolso
Condiciones de garantía
Productos relacionados
- Al elegir una selección, se actualiza la página completa.