{"product_id":"10216-2-1-fail-safe-digital-output-module-honeywell","title":"10216\/2\/1 Fail-Safe Digital Output Module | Honeywell","description":"\u003cp\u003eThe \u003cstrong\u003eHoneywell 10216\/2\/1\u003c\/strong\u003e is an 8-channel fail-safe digital output module designed for integration within Honeywell Experion PKS \/ FSC control systems. It provides loop-monitored 48 VDC outputs to drive safety-critical field loads up to 24 W per channel, ensuring high signal integrity and real-time fault detection in demanding industrial environments.\u003c\/p\u003e\n\u003ch3\u003eChannel Loop Monitoring and Power Output\u003c\/h3\u003e\n\u003cp\u003eFeaturing 8 independent output channels, the module operates with a 48 VDC, 0.5 A rating per output. Integrated loop monitoring continuously tracks field wiring and load states to detect open or short-circuit conditions, enabling proactive diagnosis of loop faults without interrupting system operation.\u003c\/p\u003e\n\u003ch3\u003eElectrical Specifications and Environmental Tolerances\u003c\/h3\u003e\n\u003cp\u003eThe module requires a nominal input voltage of 24 VDC at 0.8 A input current to power its internal processing logic. Built for harsh field deployment, it operates reliably across a wide temperature range from -40 to 70 deg C (-40 to 158 deg F) and handles relative humidity from 0 to 95% (non-condensing), backed by physical resistance to 0.05 g rms vibration and 15 g shock loads.\u003c\/p\u003e\n\u003cfigure class=\"table\"\u003e\n\u003ctable\u003e\n\u003cthead\u003e\n\u003ctr\u003e\n\u003cth\u003e\u003cstrong\u003eParameter\u003c\/strong\u003e\u003c\/th\u003e\n\u003cth\u003e\u003cstrong\u003eSpecification\u003c\/strong\u003e\u003c\/th\u003e\n\u003c\/tr\u003e\n\u003c\/thead\u003e\n\u003ctbody\u003e\n\u003ctr\u003e\n\u003ctd\u003eModel\u003c\/td\u003e\n\u003ctd\u003e10216\/2\/1\u003c\/td\u003e\n\u003c\/tr\u003e\n\u003ctr\u003e\n\u003ctd\u003eBrand\u003c\/td\u003e\n\u003ctd\u003eHoneywell\u003c\/td\u003e\n\u003c\/tr\u003e\n\u003ctr\u003e\n\u003ctd\u003eProduct Type\u003c\/td\u003e\n\u003ctd\u003eFail-Safe Digital Output Module\u003c\/td\u003e\n\u003c\/tr\u003e\n\u003ctr\u003e\n\u003ctd\u003eNumber of Channels\u003c\/td\u003e\n\u003ctd\u003e8\u003c\/td\u003e\n\u003c\/tr\u003e\n\u003ctr\u003e\n\u003ctd\u003eOutput Specification\u003c\/td\u003e\n\u003ctd\u003e48 VDC, 0.5 A loop-monitored\u003c\/td\u003e\n\u003c\/tr\u003e\n\u003ctr\u003e\n\u003ctd\u003eOutput Power\u003c\/td\u003e\n\u003ctd\u003e24 W per channel\u003c\/td\u003e\n\u003c\/tr\u003e\n\u003ctr\u003e\n\u003ctd\u003eInput Voltage\u003c\/td\u003e\n\u003ctd\u003e24 VDC\u003c\/td\u003e\n\u003c\/tr\u003e\n\u003ctr\u003e\n\u003ctd\u003eInput Current\u003c\/td\u003e\n\u003ctd\u003e0.8 A\u003c\/td\u003e\n\u003c\/tr\u003e\n\u003ctr\u003e\n\u003ctd\u003eOperating Temperature\u003c\/td\u003e\n\u003ctd\u003e-40 to 70 deg C (-40 to 158 deg F)\u003c\/td\u003e\n\u003c\/tr\u003e\n\u003ctr\u003e\n\u003ctd\u003eOperating Humidity\u003c\/td\u003e\n\u003ctd\u003e0 to 95% non-condensing\u003c\/td\u003e\n\u003c\/tr\u003e\n\u003ctr\u003e\n\u003ctd\u003eVibration Resistance\u003c\/td\u003e\n\u003ctd\u003e0.05 g rms (5 to 500 Hz)\u003c\/td\u003e\n\u003c\/tr\u003e\n\u003ctr\u003e\n\u003ctd\u003eShock Resistance\u003c\/td\u003e\n\u003ctd\u003e15 g (20 ms duration)\u003c\/td\u003e\n\u003c\/tr\u003e\n\u003ctr\u003e\n\u003ctd\u003eDimensions (L × W × H)\u003c\/td\u003e\n\u003ctd\u003e211 × 160 × 97 mm (8.3 × 6.3 × 3.8 in)\u003c\/td\u003e\n\u003c\/tr\u003e\n\u003ctr\u003e\n\u003ctd\u003eWeight\u003c\/td\u003e\n\u003ctd\u003e0.9 kg (2 lb)\u003c\/td\u003e\n\u003c\/tr\u003e\n\u003c\/tbody\u003e\n\u003c\/table\u003e\n\u003c\/figure\u003e\n\u003cp\u003eFrequently Asked Questions\u003c\/p\u003e\n\u003cp\u003eQ: What is the benefit of the loop monitoring feature on the Honeywell 10216\/2\/1?\u003c\/p\u003e\n\u003cp\u003eA: Continuous loop monitoring evaluates field wiring and connected loads in real time, detecting faults such as open circuits or wiring interruptions across its 48 VDC channels.\u003c\/p\u003e\n\u003cp\u003eQ: What are the input power requirements for this module?\u003c\/p\u003e\n\u003cp\u003eA: The module operates on a nominal supply input of 24 VDC while drawing up to 0.8 A input current.\u003c\/p\u003e","brand":"Honeywell","offers":[{"title":"Default Title","offer_id":48528896950568,"sku":"10216\/2\/1","price":315.0,"currency_code":"USD","in_stock":true}],"thumbnail_url":"\/\/cdn.shopify.com\/s\/files\/1\/0827\/6266\/2184\/files\/10216-2-1.jpg?v=1792400820","url":"https:\/\/www.powerdcs.com\/products\/10216-2-1-fail-safe-digital-output-module-honeywell","provider":"Power DCS Parts Limited","version":"1.0","type":"link"}