{"product_id":"8c-pain01-51454356-175-honeywell-series-8-analog-input-module","title":"8C-PAIN01 51454356-175 | Honeywell | Series 8 Analog Input Module","description":"\u003cp\u003eThe \u003cstrong\u003eHoneywell 8C-PAIN01 51454356-175\u003c\/strong\u003e serves as the primary \u003cstrong\u003e8C-PAIN01\u003c\/strong\u003e Analog Input Module utilized to execute field instrument analog data acquisition across Experion PKS Series 8 platforms.\u003c\/p\u003e\n\u003ch3\u003eHardware Specifications\u003c\/h3\u003e\n\u003cfigure class=\"table\"\u003e\n\u003ctable\u003e\n\u003cthead\u003e\n\u003ctr\u003e\n\u003cth\u003e\u003cstrong\u003eParameter\u003c\/strong\u003e\u003c\/th\u003e\n\u003cth\u003e\u003cstrong\u003eSpecification\u003c\/strong\u003e\u003c\/th\u003e\n\u003c\/tr\u003e\n\u003c\/thead\u003e\n\u003ctbody\u003e\n\u003ctr\u003e\n\u003ctd\u003eModel\u003c\/td\u003e\n\u003ctd\u003e8C-PAIN01 51454356-175\u003c\/td\u003e\n\u003c\/tr\u003e\n\u003ctr\u003e\n\u003ctd\u003eBrand\u003c\/td\u003e\n\u003ctd\u003eHoneywell\u003c\/td\u003e\n\u003c\/tr\u003e\n\u003ctr\u003e\n\u003ctd\u003eOrigin\u003c\/td\u003e\n\u003ctd\u003eUSA\u003c\/td\u003e\n\u003c\/tr\u003e\n\u003ctr\u003e\n\u003ctd\u003eWeight\u003c\/td\u003e\n\u003ctd\u003e0.32 - 0.45 kg\u003c\/td\u003e\n\u003c\/tr\u003e\n\u003ctr\u003e\n\u003ctd\u003eDimensions\u003c\/td\u003e\n\u003ctd\u003e157 mm x 106 mm x 35 mm\u003c\/td\u003e\n\u003c\/tr\u003e\n\u003ctr\u003e\n\u003ctd\u003eOperating Temp\u003c\/td\u003e\n\u003ctd\u003e-40 to +70 deg C\u003c\/td\u003e\n\u003c\/tr\u003e\n\u003ctr\u003e\n\u003ctd\u003ePower Consumption\u003c\/td\u003e\n\u003ctd\u003eUnspecified (24 VDC system rail)\u003c\/td\u003e\n\u003c\/tr\u003e\n\u003ctr\u003e\n\u003ctd\u003ePart Number\u003c\/td\u003e\n\u003ctd\u003e51454356-175\u003c\/td\u003e\n\u003c\/tr\u003e\n\u003ctr\u003e\n\u003ctd\u003eInput Channels\u003c\/td\u003e\n\u003ctd\u003e16 single-ended analog input channels\u003c\/td\u003e\n\u003c\/tr\u003e\n\u003ctr\u003e\n\u003ctd\u003eSignal Types Supported\u003c\/td\u003e\n\u003ctd\u003e4-20 mA, +-40 mA range, 0-10 V\u003c\/td\u003e\n\u003c\/tr\u003e\n\u003ctr\u003e\n\u003ctd\u003eInput Impedance\u003c\/td\u003e\n\u003ctd\u003e\u0026gt; 10 Mohm\u003c\/td\u003e\n\u003c\/tr\u003e\n\u003ctr\u003e\n\u003ctd\u003eAccuracy \u0026amp; Resolution\u003c\/td\u003e\n\u003ctd\u003e+-0.1% of full scale; 16-bit ADC\u003c\/td\u003e\n\u003c\/tr\u003e\n\u003ctr\u003e\n\u003ctd\u003eIsolation\u003c\/td\u003e\n\u003ctd\u003e1000 VAC RMS or +-1000 VDC\u003c\/td\u003e\n\u003c\/tr\u003e\n\u003ctr\u003e\n\u003ctd\u003eOverload Protection\u003c\/td\u003e\n\u003ctd\u003e120% for 2 seconds; 150% for 0.1 seconds\u003c\/td\u003e\n\u003c\/tr\u003e\n\u003ctr\u003e\n\u003ctd\u003eCommon Mode Rejection\u003c\/td\u003e\n\u003ctd\u003e\u0026gt; 60 dB at 120 Hz\u003c\/td\u003e\n\u003c\/tr\u003e\n\u003c\/tbody\u003e\n\u003c\/table\u003e\n\u003c\/figure\u003e\n\u003ch3\u003eProcess Instrumentation Signal Conditioning \u0026amp; CJC\u003c\/h3\u003e\n\u003cp\u003eThe 8C-PAIN01 51454356-175 module conditions low-level analog currents and voltages via its 16 single-ended channels using a 16-bit analog-to-digital converter (ADC). Designed for continuous process monitoring, the assembly incorporates galvanic isolation rated at 1000 VAC RMS (or +-1000 VDC) and dynamic common mode rejection (\u0026gt; 60 dB at 120 Hz) to eliminate field loop interference. Channel-to-channel signal processing natively accommodates 4-20 mA HART loop protocol pass-through communication alongside direct voltage measurements.\u003c\/p\u003e\n\u003ch3\u003eFrequently Asked Questions\u003c\/h3\u003e\n\u003cp\u003eQ: What is the isolation threshold between the signal terminals and system electronics on the 8C-PAIN01 51454356-175?\u003c\/p\u003e\n\u003cp\u003eA: The module provides hardware isolation rated at 1000 VAC RMS or +-1000 VDC to prevent common-mode voltage spikes from damaging backplane electronics.\u003c\/p\u003e\n\u003cp\u003eQ: How does the 8C-PAIN01 51454356-175 handle temporary current overloads on field input channels?\u003c\/p\u003e\n\u003cp\u003eA: The inputs feature built-in overload protection capable of withstanding 120% full scale for up to 2 seconds and 150% full scale for up to 0.1 seconds.\u003c\/p\u003e\n\u003cp\u003eQ: What input impedance does the module present to field transmitters?\u003c\/p\u003e\n\u003cp\u003eA: The input circuitry maintains an input impedance exceeding 10 Mohm to minimize loading errors on connected instrument loops.\u003c\/p\u003e\n\u003ch3\u003eField Installation Guidelines\u003c\/h3\u003e\n\u003cul\u003e\n\u003cli\u003e\n\u003cstrong\u003eIOTA Chassis Installation\u003c\/strong\u003e: Align the 8C-PAIN01 51454356-175 card with the dedicated slot on the Series 8 Input Output Termination Assembly (IOTA) carrier and seat the backplane pins before securing retention hardware.\u003c\/li\u003e\n\u003cli\u003e\n\u003cstrong\u003eShield Cable Earthing\u003c\/strong\u003e: Terminate single-ended analog signal cable drain wires directly to the main cabinet grounding bus to maintain shield continuity and noise rejection.\u003c\/li\u003e\n\u003cli\u003e\n\u003cstrong\u003eWiring Routing Restrictions\u003c\/strong\u003e: Keep analog input signal conductors isolated from AC power distribution lines and high-current relay cabling within panel wiring ducts.\u003c\/li\u003e\n\u003c\/ul\u003e","brand":"Honeywell","offers":[{"title":"Default Title","offer_id":52312941855016,"sku":"8C-PAIN01 51454356-175","price":315.0,"currency_code":"USD","in_stock":true}],"thumbnail_url":"\/\/cdn.shopify.com\/s\/files\/1\/0827\/6266\/2184\/files\/8C-PAIMA151454473-175_a217e19b-b043-4a0d-b81d-2139b04f8d8c.png?v=1788252995","url":"https:\/\/www.powerdcs.com\/products\/8c-pain01-51454356-175-honeywell-series-8-analog-input-module","provider":"Power DCS Parts Limited","version":"1.0","type":"link"}