{"product_id":"900c53-0001-honeywell-analog-output-module","title":"900C53-0001 | Honeywell | Analog Output Module","description":"\u003cp\u003eConfigured for multi-channel analog output signal conditioning within ControlEdge HC900 architectures, the \u003cstrong\u003eHoneywell 900C53-0001\u003c\/strong\u003e (\u003cstrong\u003e900C53-0001\u003c\/strong\u003e Analog Output Module) provides direct physical\/electrical execution of 4-20 mA and 0-10 V command loops.\u003c\/p\u003e\n\u003ch3\u003eHardware Specifications\u003c\/h3\u003e\n\u003cfigure class=\"table\"\u003e\n\u003ctable\u003e\n\u003cthead\u003e\n\u003ctr\u003e\n\u003cth\u003e\u003cstrong\u003eParameter\u003c\/strong\u003e\u003c\/th\u003e\n\u003cth\u003e\u003cstrong\u003eSpecification\u003c\/strong\u003e\u003c\/th\u003e\n\u003c\/tr\u003e\n\u003c\/thead\u003e\n\u003ctbody\u003e\n\u003ctr\u003e\n\u003ctd\u003eModel\u003c\/td\u003e\n\u003ctd\u003e900C53-0001\u003c\/td\u003e\n\u003c\/tr\u003e\n\u003ctr\u003e\n\u003ctd\u003eBrand\u003c\/td\u003e\n\u003ctd\u003eHoneywell\u003c\/td\u003e\n\u003c\/tr\u003e\n\u003ctr\u003e\n\u003ctd\u003eOrigin\u003c\/td\u003e\n\u003ctd\u003eUSA\u003c\/td\u003e\n\u003c\/tr\u003e\n\u003ctr\u003e\n\u003ctd\u003eOperating Temp\u003c\/td\u003e\n\u003ctd\u003e-40 to +60 deg C\u003c\/td\u003e\n\u003c\/tr\u003e\n\u003ctr\u003e\n\u003ctd\u003eStorage Temp\u003c\/td\u003e\n\u003ctd\u003e-40 to +85 deg C\u003c\/td\u003e\n\u003c\/tr\u003e\n\u003ctr\u003e\n\u003ctd\u003ePower Consumption\u003c\/td\u003e\n\u003ctd\u003eController backplane supplied DC power\u003c\/td\u003e\n\u003c\/tr\u003e\n\u003ctr\u003e\n\u003ctd\u003eProduct Type\u003c\/td\u003e\n\u003ctd\u003eAnalog Output Module\u003c\/td\u003e\n\u003c\/tr\u003e\n\u003ctr\u003e\n\u003ctd\u003eChannels\u003c\/td\u003e\n\u003ctd\u003e4 Independent Channels\u003c\/td\u003e\n\u003c\/tr\u003e\n\u003ctr\u003e\n\u003ctd\u003eOutput Type\u003c\/td\u003e\n\u003ctd\u003e4-20 mA, 0-10 V\u003c\/td\u003e\n\u003c\/tr\u003e\n\u003ctr\u003e\n\u003ctd\u003eResolution\u003c\/td\u003e\n\u003ctd\u003e12-bit Digital-to-Analog conversion\u003c\/td\u003e\n\u003c\/tr\u003e\n\u003ctr\u003e\n\u003ctd\u003eAccuracy\u003c\/td\u003e\n\u003ctd\u003e+\/-0.1% of full scale\u003c\/td\u003e\n\u003c\/tr\u003e\n\u003ctr\u003e\n\u003ctd\u003eIsolation\u003c\/td\u003e\n\u003ctd\u003e1500 V RMS between field and logic\u003c\/td\u003e\n\u003c\/tr\u003e\n\u003ctr\u003e\n\u003ctd\u003eResponse Time\u003c\/td\u003e\n\u003ctd\u003e\u0026lt; 2 ms\u003c\/td\u003e\n\u003c\/tr\u003e\n\u003ctr\u003e\n\u003ctd\u003eSystem Compatibility\u003c\/td\u003e\n\u003ctd\u003eHoneywell ControlEdge HC900 hybrid controller\u003c\/td\u003e\n\u003c\/tr\u003e\n\u003c\/tbody\u003e\n\u003c\/table\u003e\n\u003c\/figure\u003e\n\u003ch3\u003eChannel-to-Channel Isolation and 4-20 mA HART Loop Protocol\u003c\/h3\u003e\n\u003cp\u003eThe module incorporates 1500 V RMS optical isolation barriers between field output loops and internal system logic, preventing ground loop potential shifts and common-mode transient spikes from corrupting DAC reference levels. High-speed 12-bit digital-to-analog conversion stages condition the analog outputs while supporting superimposed 4-20 mA HART protocol communication signals for bi-directional diagnostics with intelligent final control elements.\u003c\/p\u003e\n\u003ch3\u003eFrequently Asked Questions\u003c\/h3\u003e\n\u003cp\u003eQ: Does the 900C53-0001 output module support online hot-swapping in the HC900 rack?\u003c\/p\u003e\n\u003cp\u003eA: Rack power must be completely de-energized before removing or inserting output modules to prevent backplane bus errors and hardware damage.\u003c\/p\u003e\n\u003cp\u003eQ: What output signal configurations are supported by the 4 channels?\u003c\/p\u003e\n\u003cp\u003eA: Each channel can be configured to drive either 4-20 mA current loops or 0-10 V voltage signals depending on application requirements.\u003c\/p\u003e\n\u003ch3\u003eField Installation Guidelines\u003c\/h3\u003e\n\u003col\u003e\n\u003cli\u003eVerify that incoming cabinet rack power is isolated and locked out prior to handling or installing the module.\u003c\/li\u003e\n\u003cli\u003eAlign module card edges with the designated I\/O slot guide rails on the HC900 controller chassis.\u003c\/li\u003e\n\u003cli\u003ePush the module firmly inward until rear backplane connectors mate completely with the header pins.\u003c\/li\u003e\n\u003cli\u003eTerminate field actuator signal wiring to the corresponding terminal blocks, ensuring correct polarity matching across all active channels.\u003c\/li\u003e\n\u003c\/ol\u003e","brand":"Honeywell","offers":[{"title":"Default Title","offer_id":67864475337000,"sku":"900C53-0001","price":315.0,"currency_code":"USD","in_stock":true}],"thumbnail_url":"\/\/cdn.shopify.com\/s\/files\/1\/0827\/6266\/2184\/files\/900C53-0001_Cocoai.png?v=1791618913","url":"https:\/\/www.powerdcs.com\/products\/900c53-0001-honeywell-analog-output-module","provider":"Power DCS Parts Limited","version":"1.0","type":"link"}