Allen Bradley 140CMN6300 Manual Motor Starter Breaker

Specifications

  • Manufacturer: Allen Bradley

  • Product No.: 140CMN6300

  • Condition: 10 Items in Stock

  • Product Type: Manual Motor Starter Breaker

  • Product Origin: USA

  • Payment:T/T, Western Union

  • Weight: 480g

  • Shipping port: Xiamen

  • Warranty: 12 months

Product details

Description

Allen-Bradley 140-CMN-6300 Manual Motor Starter Breaker

Overview
The 140-CMN-6300 is a Motor Protection Circuit Breaker from Allen-Bradley’s Bulletin 140 series. Designed for reliable protection of industrial motors, it features a rated operational current of 63 A and a magnetic release current of 890 A. This breaker ensures both overload and short-circuit protection while enabling manual circuit isolation for maintenance and safety procedures.

Technical Specifications

  • Brand: Allen-Bradley / Rockwell Automation

  • Series: 140M Circuit Breakers

  • Part Number/Catalog No.: 140-CMN-6300

  • IEC/EN60947-1,-2 Compliance: CE Marked

  • CSA, C22.2 No.14 Compliance: CSA Certified

  • UL508 Compliance: cULus Listed (File No. E54612, NLRV(7); E205542, NKJH(7); E197878, DIVQ(7))

  • Compatible Applications: Motor branch circuit disconnect, branch-circuit protection, short-circuit (magnetic) protection, overload (thermal) protection, manual switching

  • Max Current: 90 A

  • Trip Setting: 40–63 A

  • Current Rating: 16–90 A

  • Operating Voltage: 230–690 VAC

  • Short-Circuit Protection: Yes

  • Standard Magnetic Trip: Yes

  • High Magnetic Trip: Yes

  • Wire Insulation Rating: 75 °C

  • Torque: 6–10 Nm (55–90 lb-in)

  • Overload Protection: Yes

  • Trip Class: 10

  • Mechanical Operations: 30,000

  • Rated Operational Current (Ie): 63 A

  • Electrical (Ie max.) Operations: 5,000

  • Magnetic Release Current: 890 A

  • Switching Frequency: 20 operations/hour

Description
The 140-CMN-6300 is engineered for motor protection and circuit isolation. It is ideal for disconnecting motor branch circuits, providing overload (thermal) protection, and short-circuit (magnetic) protection.

The breaker features a manually operated lever for engaging or disengaging circuits. Trip settings are adjustable from 40–63 A using a precision screwdriver. The magnetic release is rated at 890 A, and the ultimate short-circuit breaking capacity ranges from 4 A to 50 A depending on voltage.

For proper installation, use #8–14 AWG copper wire with a maximum insulation rating of 75 °C, and tighten connections to a torque of 6–10 Nm (55–90 lb-in). The breaker also allows for safe maintenance procedures, enabling circuit isolation through Lock-Out/Tag-Out (LOTO) practices.

Switching Ratings for Standard Three-Phase Motors:

  • 230/240 VAC: 13/20

  • 400/415 VAC: 25/32

  • 500 VAC: 30/40

  • 690 VAC: 37/55

 