Allen Bradley 140CMN6300 Manual Motor Starter Breaker
Specifications
Manufacturer: Allen Bradley
Product No.: 140CMN6300
Condition: 10 Items in Stock
Product Type: Manual Motor Starter Breaker
Product Origin: USA
Payment:T/T, Western Union
Weight: 480g
Shipping port: Xiamen
Warranty: 12 months
Product details
Description
Allen-Bradley 140-CMN-6300 Manual Motor Starter Breaker
Overview
The 140-CMN-6300 is a Motor Protection Circuit Breaker from Allen-Bradley’s Bulletin 140 series. Designed for reliable protection of industrial motors, it features a rated operational current of 63 A and a magnetic release current of 890 A. This breaker ensures both overload and short-circuit protection while enabling manual circuit isolation for maintenance and safety procedures.
Technical Specifications
-
Brand: Allen-Bradley / Rockwell Automation
-
Series: 140M Circuit Breakers
-
Part Number/Catalog No.: 140-CMN-6300
-
IEC/EN60947-1,-2 Compliance: CE Marked
-
CSA, C22.2 No.14 Compliance: CSA Certified
-
UL508 Compliance: cULus Listed (File No. E54612, NLRV(7); E205542, NKJH(7); E197878, DIVQ(7))
-
Compatible Applications: Motor branch circuit disconnect, branch-circuit protection, short-circuit (magnetic) protection, overload (thermal) protection, manual switching
-
Max Current: 90 A
-
Trip Setting: 40–63 A
-
Current Rating: 16–90 A
-
Operating Voltage: 230–690 VAC
-
Short-Circuit Protection: Yes
-
Standard Magnetic Trip: Yes
-
High Magnetic Trip: Yes
-
Wire Insulation Rating: 75 °C
-
Torque: 6–10 Nm (55–90 lb-in)
-
Overload Protection: Yes
-
Trip Class: 10
-
Mechanical Operations: 30,000
-
Rated Operational Current (Ie): 63 A
-
Electrical (Ie max.) Operations: 5,000
-
Magnetic Release Current: 890 A
-
Switching Frequency: 20 operations/hour
Description
The 140-CMN-6300 is engineered for motor protection and circuit isolation. It is ideal for disconnecting motor branch circuits, providing overload (thermal) protection, and short-circuit (magnetic) protection.
The breaker features a manually operated lever for engaging or disengaging circuits. Trip settings are adjustable from 40–63 A using a precision screwdriver. The magnetic release is rated at 890 A, and the ultimate short-circuit breaking capacity ranges from 4 A to 50 A depending on voltage.
For proper installation, use #8–14 AWG copper wire with a maximum insulation rating of 75 °C, and tighten connections to a torque of 6–10 Nm (55–90 lb-in). The breaker also allows for safe maintenance procedures, enabling circuit isolation through Lock-Out/Tag-Out (LOTO) practices.
Switching Ratings for Standard Three-Phase Motors:
-
230/240 VAC: 13/20
-
400/415 VAC: 25/32
-
500 VAC: 30/40
-
690 VAC: 37/55