CC-PAIH02 51405038-375 Experion PKS High-Level Analog Input Module | Honeywell
Specifications
Manufacturer: Honeywell
Product No.: CC-PAIH02 51405038-375
Condition: 10 Items in Stock
Product Type: Analog Input Modules
Product Origin: USA
Payment:T/T, Western Union
Weight: 450g
Shipping port: Xiamen
Warranty: 12 months
Product details
Description
Configured for high-level signal acquisition in Experion PKS Series-C control systems, the Honeywell CC-PAIH02 51405038-375 (CC-PAIH02 Analog Input Module) provides direct physical/electrical execution. It handles 16 analog input channels across Input/Output Termination Assembly (IOTA) bus structures.
Hardware Specifications
| Parameter | Specification |
|---|---|
| Model | CC-PAIH02 51405038-375 |
| Brand | Honeywell |
| Origin | USA |
| Operating Temp | -40 to +70 deg C |
| Power Consumption | ~6 W typical |
| Channels | 16 channels (12 single-ended, 4 differential) |
| Input Ranges | 0-5 V, 1-5 V, 0.4-2 V, 4-20 mA (via internal 250 ohm resistor) |
| A/D Converter Resolution | 16 bits |
| Hardware Accuracy | +/- 0.075% of full scale (at 23.5 deg C +/- 2 deg C) |
| Scan Rate | 50 ms |
| Input Impedance | >10 Mohm (for voltage inputs) |
| Common Mode Rejection Ratio | 70 dB (DC to 60 Hz) |
| Normal Mode Rejection Ratio | 19 dB (at 60 Hz) |
Channel-to-Channel Isolation and 4-20 mA HART Loop Protocol Execution
The Honeywell CC-PAIH02 51405038-375 analog input module digitized process variables using a high-precision 16-bit A/D converter across a fast 50 ms scan cycle. Each channel interfaces directly with 2-wire or self-powered field transmitters utilizing the 4-20 mA HART loop protocol, as well as 0-5 V, 1-5 V, and 0.4-2 V voltage signals. The internal circuit architecture maintains robust signal conditioning and noise suppression, delivering 70 dB CMRR to safeguard backplane communications against field-side electrical interference and ground loop offsets.
Frequently Asked Questions
Q: How does the CC-PAIH02 module convert 4-20 mA current signals into internal voltage measurements?
A: Current loops are converted into voltage signals internally across precision 250 ohm dropping resistors integrated within the module circuit path.
Q: Can single-ended and differential field inputs be mixed on the same CC-PAIH02 module?
A: Yes, the module natively accommodates up to 12 single-ended channels and 4 differential channels according to the terminal assignments on the corresponding IOTA assembly.
Field Installation Guidelines
- Mount the Series-C IOTA base securely to the cabinet frame or DIN rail prior to inserting the CC-PAIH02 module.
- Align the module edge connector pins carefully with the IOTA connector slot and push firmly until the locking tabs snap into place.
- Terminate 4-20 mA signal wires onto the designated IOTA screw terminals, verifying correct polarity for 2-wire loop-powered or self-powered field transmitters.
- Separate low-voltage analog signal cables from high-voltage AC power wiring by at least 200 mm to minimize electromagnetic interference.
- Connect cable shield drains to the cabinet single-point grounding bar to establish effective ground loop isolation.