CC-TFB402 Honeywell Experion PKS Series C FIM 4 IOTA Board

Specifications

  • Manufacturer: Honeywell

  • Product No.: CC-TFB402 51308309-275

  • Condition: 10 Items in Stock

  • Product Type: Fieldbus Interface Assemblies

  • Product Origin: USA

  • Payment:T/T, Western Union

  • Weight: 180g

  • Shipping port: Xiamen

  • Warranty: 12 months

Product details

Description

The Honeywell CC-TFB402, also cataloged as the CC-TFB402 PC Board PLC/Add-On Board, operates as a dedicated hardware component for fieldbus interface module signal termination within Experion PKS Series C C300 controller architectures.

Hardware Specifications

Parameter Specification
Model CC-TFB402 (Part Number: 51308309-275)
Brand Honeywell
Origin USA
Weight 0.18 kg (0.40 lbs)
Dimensions Standard Series C IOTA board form factor
Operating Temp -40 to +70 deg C housing environmental envelope
Power Consumption Passive backplane routing assembly (0 W logic dissipation)
Interface Type Fieldbus Interface Module (FIM 4) IOTA assembly
Carrier Compatibility Experion PKS Series C I/O termination assembly
Product Category Fieldbus Interface Assemblies

FOUNDATION Fieldbus Connectivity & Process Signal Isolation

The CC-TFB402 IOTA board establishes physical signal routing between fieldbus trunks and the FIM 4 processing module. Designed to interface directly with FOUNDATION Fieldbus / Profibus PA connectivity networks, the circuit board provides high channel-to-channel isolation and surge filtering to maintain communications integrity across process loops. Differential trunk lines terminate directly at the board screw terminals, shielding internal bus electronics from field-induced electrical transients and ground potential shifts.

Frequently Asked Questions

Q: Does replacing the CC-TFB402 IOTA board require powering down the connected FIM 4 processing module?

A: No, the IOTA board layout allows the active FIM 4 module to be unseated while field wiring remains anchored, supporting hot-swap module maintenance.

Q: What function does the CC-TFB402 perform within the Experion PKS Series C architecture?

A: It functions as the physical Input Output Termination Assembly (IOTA) dedicated to routing fieldbus trunk signals to the FIM 4 module.

Q: Are terminating resistors integrated directly into the CC-TFB402 circuit board?

A: Fieldbus segment termination depends on network topology; external or jumper-selected bus terminators must be verified on the IOTA board according to FOUNDATION Fieldbus physical layer specifications.

Field Installation Guidelines

  1. Mount the CC-TFB402 board onto the Series C vertical channel carrier rail until all backplane retaining pins snap into place.
  2. Terminate fieldbus trunk cables to the dedicated screw terminal blocks, observing strict polarity for positive (+) and negative (-) signal lines.
  3. Connect cable shield drains directly to the local earth grounding bar on the cabinet frame to suppress high-frequency electromagnetic noise.
  4. Align the FIM 4 module guide pins with the CC-TFB402 multi-pin connector and press firmly to seat the active electronics onto the IOTA.

How to Get a Quote